MTU 12 V 4000 Lx4 Operating Instructions Manual page 102

Gas engine
Table of Contents

Advertisement

1.4540.033 – Battery Volt High Error
Red alarm. Initiated by TecJet.
Cause
Supply voltage has reached
maximum limit value.
1.4540.034 – FGT High Limit Error
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for
operation.
1.4540.035 – Delta P High Limit Error
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for
operation.
1.4540.036 – FGP High Limit Error
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for
operation.
1.4540.037 – Watchdog Reset
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for
operation.
1.4540.038 – CAN Flow Demand Failed
Red alarm. Initiated by TecJet.
Cause
TecJet setting is not correct.
1.4540.040 – TecJet Shutdown
Red alarm. Initiated by TecJet.
Cause
TecJet combined alarm. At least
one further TecJet alarm is
present.
102 | Troubleshooting | MS15027/00E 2013-10
Corrective action
1. Check supply voltage.
2. Check cabling.
Corrective action
u Restart TecJet.
Corrective action
u Restart TecJet.
Corrective action
u Restart TecJet.
Corrective action
u Restart TecJet.
Corrective action
u Check setting.
Corrective action
u Rectify cause of alarm.