Detachments; Indoor Unit - Toshiba RAV-SM562MUT-E Service Manual

Air conditioner split type
Hide thumbs Also See for RAV-SM562MUT-E:
Table of Contents

Advertisement

13-1. Indoor Unit

Ceiling panel: RBC-UM11PG(W)E
Preparing work:
1. Before work, be sure to stop the power supply of the air conditioner and turn off switch of the power supply
breaker. (Otherwise an electric shock may be caused.)
2. Be sure to put on the gloves when working; otherwise an injury may be caused with parts sharp edges etc.
No.
Part name
1. Detachment
1
Suction grille
1) Slide hooks (2 positions) of the suction grille
2) Take off the strap that connects the panel
2. Attachment
1) Hook shaft of the suction grille to the panel.
2) Hook strap of the suction grille to the original position of the panel.
3) Close the suction grille and slide the hooks outward to fix it.
2
Electric parts
1. Detachment
cover
1) Perform work of procedure
2) Take off screws (Ø4 × 10, 3 pcs.) fixing the
3) Remove the electric parts cover from the
2. Attachment
1) Close the electric parts cover and hook the
2) Tighten the fixing screws. (Ø4 × 10, 3 pcs.)
Tel: 01823 665660
Heronhill - for all your Toshiba requirements

13. DETACHMENTS

Procedure
to inner side, and then hang down the
suction grille.
and the suction grille, and then lift up shaft of
the suction grille to remove the suction grille.
electric parts cover.
temporary hanging hook of the electric parts
cover, and then open the cover.
cover hole to the temporary hanging hook.
– 76 –
www.heronhill.co.uk
Suction grille
Hook of suction grille
Hook of
fall-preventive strap
-1.
1
Screws
Unnecessary to remove this hook.
Remarks
Ceiling panel
Hook hole of ceiling panel
Temporary hanging hook
Screw
Fax: 01823 665807

Advertisement

Table of Contents
loading

Table of Contents