Toshiba RAV-SM562MUT-E Service Manual page 63

Air conditioner split type
Hide thumbs Also See for RAV-SM562MUT-E:
Table of Contents

Advertisement

DN
Item
01
Filter sign lighting time
02
Dirty state of filter
03
Central control address
06
Heating suction temp shift
0F
Cooling only
10
Type
11
Indoor unit capacity
12
Line address
13
Indoor unit address
14
Group address
19
1E
Temp difference of
automatic cooling/heating
mode selection COOL →
HEAT, HEAT → COOL
28
Automatic restart of power
failure
2A
Option
2b
Thermo output selection
ƒ
(T10
)
2E
Option
30
Option
31
Option
32
Sensor selection
33
Temperature indication
40
Option
5d
High ceiling selection (Air
volume selection)
60
Timer set
(Wired remote controller)
8b
Correction of high heat
feeling
Tel: 01823 665660
Heronhill - for all your Toshiba requirements
Item No. (DN) table (Selection of function)
Description
0000 : None
0002 : 2500H (4-Way/Duct/Ceiling Type)
0000 : Standard
0001 : High degree of dirt (Half of standard time)
0001 : No.1 unit
to
0064 : No.64 unit
0099 : Unfixed
0000 : No shift
0001 : +1°C
0002 : +2°C
to
0010 : -10°C
0000 : Heat pump
0001 : Cooling only (No display of [AUTO] [HEAT])
0014 : SM562MUT-E
0000 : Unfixed
0009 : 562 type
0012 : 802 type
0015 : 1102 type
0017 : 1402 type
0001 : No.1 unit
to
0030 : No.30 unit
0001 : No.1 unit
to
0064 : No.64 unit
0000 : Individual
0001 : Master of group
0002 : Sub of group
0000 : 0 deg
to
0010 : 10 deg
(For setup temperature, reversal of
COOL/HEAT by ± (Data value)/2)
0000 : None
0001 : Restart
0000 : Indoor thermo ON
0001 : Output of outdoor comp-ON receiving
0000 : Body TA sensor
0001 : Remote controller sensor
0000 : °C (celsius)
0001 : °F (Fahrenheit)
0000 : Standard (Below 3.2m)
0001 : Standard (Below 3.4m)
0003 : Standard (Below 3.5m)
0000 : Available (Operable)
0001 : Unavailable (Operation prohibited)
0000 : None
0001 : Correction
– 63 –
www.heronhill.co.uk
(Up to recommendation + 6)
Fax: 01823 665807
At shipment
0002 for D.I. and S.D.I.
models
0000 : Standard
0099 : Unfixed
0002 : +2°C
(Floor type 0000: 0°C)
0000 : Shared for
cooling/heating
According to model type
According to capacity type
0099 : Unfixed
0099 : Unfixed
0099 : Unfixed
0003 : 3 deg
(Ts±1.5)
0000 : None
0002 : Default
0000: Thermo. ON
0000 : Default
0000 : Default
0000 : Default
0000 : Body sensor
0000 : °C
0003 : Default
0000 : Standard
0000 : Available
0000 : None

Advertisement

Table of Contents
loading

Table of Contents