Toshiba RAV-SM562MUT-E Service Manual page 49

Air conditioner split type
Hide thumbs Also See for RAV-SM562MUT-E:
Table of Contents

Advertisement

[P29 error]
Are connections of
cable/connector normal?
YES
Is compressor normal?
YES
[H03 error]
Are cablings of power and
current sensor normal?
YES
Check IPDU.
®
Defect
Replace
Tel: 01823 665660
Heronhill - for all your Toshiba requirements
NO
NO
Is not earthed?
NO
Is not winding shorted?
(Is resistance between windings 0.6 to 1.2
NO
Is not winding opened?
NO
Check IPDU P.C. board.
®
Defect
Replace
NO
* For RAV-SM562AT-E, replace control P.C. board.
– 49 –
www.heronhill.co.uk
Check and correct circuit cabling
such as cabling to compressor.
YES
Compressor error
YES
W
Compressor error
?)
YES
Compressor error
* For RAV-SM562AT-E, replace control P.C. board.
Check and correct circuit cables.
Fax: 01823 665807
®
Replace
®
Replace
®
Replace

Advertisement

Table of Contents
loading

Table of Contents