[F01 error]
Is connection of TCJ sensor connector
(Indoor P.C. board CN102) normal?
YES
Are characteristics of
TCJ sensor resistance value normal?
YES
Check indoor P.C. board
®
(MCC-1402).
Defect
Replace
[P26 error]
Is power voltage normal?
Are connections of
cabling/connector normal?
YES
Does RY01 relay of
IPDU operate?
NO
YES
Is not AC fuse fused?
Replace IPDU.
* Replace control P.C. board
of RAV-SM562AT-E.
Check IPDU.
Defect
Tel: 01823 665660
Heronhill - for all your Toshiba requirements
NO
NO
* Refer to Characteristics-2.
NO
YES
NO
* For RAV-SM562AT-E,
check RY01 on the control P.C. board.
YES
Are not "P26" and "14" errors output
removing 3P connector of compressor?
* Single-phase type is not
provided to RAV-SM562AT-E.
NO
®
Replace
– 48 –
www.heronhill.co.uk
Improve the power supply line.
Check and correct circuit cables.
Correct connection of connector.
Check and correct reactor connection.
when an operation is performed by
YES
Is compressor normal?
YES
Check rare short of compressor trouble.
Defect
Correct connection of connector.
Replace TCJ sensor.
NO
Replace IPDU.
* Replace control P.C. board
of RAV-SM562AT-E.