9-2-2. Outline of Main Controls
1. Pulse Modulating V alve (PMV ) control
1) For PMV with 50 to 500 pulses during operation, respectively.
2) In cooling operation, PMV is controlled with the temperature difference between TS sensor and TC
sensor.
3) In heating operation, PMV is controlled with the temperature difference between TS sensor and TE
sensor.
4) For the temperature difference in items 2) and 3), 1 to 5K is aimed as the target in both cooling and
heating operations.
5) When the cycle excessively rose in both cooling and heating operations, PMV is controlled by TD
sensor.
The aimed value is usually 103°C for SM56, SM80 and 100°C for SM110, SM140 in both cooling and
heating operations.
A sensor trouble may cause a liquid back-flow or abnormal overheat resulting in excessive shortening of the
compressor life. In a case of trouble on the compressor, be sure to check there is no error in the resistance
value an the refrigerating cycle of each sensor after repair and then start the operation.
2. Discharge temperature release control
1) This function controls the operation frequency, that
is, lowers the operation frequency when the
discharge temperature has not lower or the
discharge temperature has rapidly risen during
PMV control. It subdivides the frequency control
up to a unit of 0.6 Hz to stabilize the cycle.
2) When the discharge temperature is detected in an
abnormal stop zone, the unit stops the compres-
sor and restarts after 2 minutes 30 seconds. The
error counter is cleared when it has continued the
operation for 10 minutes.
If the abnormal stop zone has been detected by 4
times without clearing of counter, an error "P03" is
displayed.
* The cause is considered as excessively little
amount of refrigerant, defective PMV, or clogging
of cycle.
a
SM56, SM80
117
SM110, SM140
111
3. Current release control
The output frequency and the output voltage are
controlled by AC current value detected by T02 on the
outdoor P .C. board so that input current of the inverter
does not exceed the specified value.
SM56
Objective model
COOL HEAT COOL HEAT COOL HEAT COOL HEAT
I1 value [A]
10.1
Tel: 01823 665660
Heronhill - for all your Toshiba requirements
REQUIREMENT
[°C]
b
c
d
e
107
103
100
93
106
100
95
90
SM80
12.0
12.2
14.0
18.9
– 76 –
www.heronhill.co.uk
TD [˚C]
Error stop ("P03" display with 4 times of error counts)
a
b
c
d
e
As command is
Current [A]
I1
I1–0.5
Normal operation
SM110
SM140
19.7
19.7
19.7
Frequency down
Frequency holding
Frequency slow-up
(Up to command)
Frequency down
Hold
Hold
Fax: 01823 665807