Toshiba RAV-SM563UT-E Service Manual/Integration page 144

Air-conditioner split type
Hide thumbs Also See for RAV-SM563UT-E:
Table of Contents

Advertisement

No.
Part name
Inverter
7) Remove connectors which are connected
assembly
from the cycle P .C. board to other parts.
(Continued)
Compressor lead: Remove terminal cover of
the compressor, and remove the lead wire
from terminal of the compressor.
*(Note 1)
Remove the connectors by releasing lock of the
housing.
8) Remove various lead wires.
9) Cut off tie lap which fixes various lead wires
to the inverter assembly.
Cycle P .C.
1) Remove connectors and lead wires which
board
are connected from the cycle P .C. board to
other parts.
1. Connector
*(Note 1)
Remove the connector while releasing locking of
the housing.
2) Mount a new cycle P .C. board.
Tel: 01823 665660
Heronhill - for all your Toshiba requirements
Procedure
CN600: TD sensor (3P: White)
CN601: TO sensor (2P: White)
CN604: TE sensor (2P: White) *Note 1)
CN605: TS sensor (3P: White) *(Note 1)
CN301: Outdoor fan (3P: White) *(Note 1)
CN300: Position detection (5P: White)
CN500: Case thermo. (2P: Blue) *(Note 1)
CN702: P .M.V. (Pulse Motor Valve)
coil (6P: White) *(Note 1)
Relay connector:
4-way valve (3P: Yellow) *(Note 1)
Relay connector:
Reactor 2 pcs. (2P: White) *(Note 1)
CN01 : Connection with IPDU P .C. board
(5P , Red) *(Note 1)
CN02 : Indoor/Outdoor connection
terminal block (5P, Black)
CN03 : Connection with IPDU P .C. board
(3P , White) *(Note 1)
CN04 : Connection with IPDU P .C. board
(2P , White) *(Note 1)
CN700 : 4-way valve (3P , Yellow) *(Note 1)
CN800 : Connection with IPDU P .C. board
(5P , Red) *(Note 1)
– 144 –
www.heronhill.co.uk
Remarks
Inverter box (Metal sheet)
P.C. board
base
Cycle control
P.C. board
assembly
Inverter
control
P.C. board
assembly
Cycle control
P.C. board
assembly
Fax: 01823 665807