Wood Fireplace Specifics-Minimum Clearances - Regency L850B Owners & Installation

Montrose wood fireplace
Table of Contents

Advertisement

installation
WOOD FIREPLACE SPECIFICS AND MINIMUM CLEARANCES
Framing Guide
Unit cavity to be open into the roof cavity.
Cavity Must be open extending to attic. No ceiling within cavity.
Wall Cladding
Non-combustible material such as 9mm cement sheeting
must be used on front wall of zero enclosure.
1597mm
1470mm
10
Hearth Requirements
Hearth needs to be 6mm thick and 1470mm wide and 995mm deep to allow for
300mm leading edge. W e do recommend though that your non-combustible hearth
extend 900mm in front of the unit. This allows the floor to be protected when the
door is fully open in case of ember drop.
Floor Protection
The floor protector must be a minimum of 300mm deep in front of the appliance
base. However it is highly recommended due to the width of the appliance door
that this dimension is increased in case of ember or hot ash spillage.
The floor protector must also be a minimum of 1470mm wide by 945 mm deep
x 6 mm thick cement fiber sheet with a thermal resistance value of 0.8m
per 4mm thickness.
The appliance must be installed on a non combustible stand 300mm above the
hearth.
6MM THICK CEMENT FIBRE
SHEET AS HEARTH
1470MM x 995MM
2
kw
750mm
Montrose Woodfire