Insert Placement; Zero-Clearance Fireplace Requirements - Vermont Castings 30ILDVNV Installation And Operating Instructions Manual

Ildv series direct vent gas fireplace insert
Table of Contents

Advertisement

CLEARANCES

INSERT PLACEMENT

The insert must be placed within a code-conforming
ILDV20
masonry fireplace or a tested and listed zero-clear-
ance (UL-127, solid fuel) fireplace. Repair any fireplace
damage prior to installation.
Because the insert uses a circulation blower, clean the
fireplace, smoke shelf and chimney before installing.
This heater may be placed in a bedroom. Please be
(572 mm)
aware of the large amount of heat this appliance pro-
duces when determining a location.
ILDV30
30ILDV
(711 mm)
Figure 4
Minimum Openings
ZERO-CLEARANCE (METAL) FIREPLACE
REQUIREMENTS
The damper and grate must be removed.
ILDV40
The smoke shelf, internal baffles, screen, refractory and
metal or glass doors may be removed (if applicable).
Do not remove or alter the insulation or any structured
rigid frame members (metal sides, floor, door frames,
face of the fireplace, etc.).
(787 mm)
IMPORTANT: Please review the following carefully.
It is normal for inserts fabricated of steel to give off some
expansion and/or contraction noises during the start up or
cool down cycle. Similar noises are found with your furnace
heat exchanger or car engine.
It is not unusual for your insert to give off some odor the
first time it is burned. This is due to the curing of the paint
and any undetected oil from the manufacturing process.
Please ensure that your room is well ventilated. OPEN
ALL WINDOWS DURING INITIAL BURN OFF/CURING
PHASE.
Burn your insert for at least six (6) hours on "HIGH" the
first time you use it. Place the fan in the "OFF" position
during this time.
20306755
15¹⁄₈"
(384 mm)
22¹⁄₂"
14"
(356 mm)
18"
(457 mm)
28"
16"
(406 mm)
23"
(584 mm)
31"
16¹⁄₂"
(419 mm)
fp1959
FIREBOX DIMS
18"
• Installer must attach red warning plate to the inside of the
(457 mm)
firebox of fireplace with screws supplied.
• Do not cut any sheet metal parts of the fireplace in which
this gas fireplace insert is installed. THIS IS STRICTLY
PROHIBITED!
• If factory-built fireplace has no gas access hole(s)
provided, drill a 1.5" (37.5 mm) or less through lower sides
or bottom of firebox. You must plug the access hole with
noncombustible insulation after gas supply line has been
installed.
• If your factory-built fireplace has air passages on the
face for zero clearance, DO NOT BLOCK THESE
PASSAGES!
21"
(533 mm)
23¹⁄₂"
(597 mm)
Figure 5
Metal Fireplace Zero-Clearance Requirements
30ILDV Series Gas Fireplace Insert
WARNING
Insulation
Shelf
Masonry Lining or Refractory
Grate
Masonry Lining or Refractory
Fp1921
zero clearance requirements
9/08
9