General

1. Structure supporting unit must be designed to support both the unit and the fluid.
2. Level mounting is necessary to ensure proper fluid distribution through the coil as well
3. Water piping must comply with local codes. Correct pipe sizing will help reduce
4. In case of doubt, consult the manufacturer for the dry cooler fluid pressure drop at the
5. Provide sufficient valves and unions to permit easy access to parts subject to wear and
6. After fluid piping is completed, all joints should be leak tested.
7. Where city water make-up is required, follow local codes, making certain that
8. Select wire in accordance with nameplate data and local codes.

Piping Installation

The piping system should provide maximum leak prevention. Weld or sweat joints should
be used where possible. The fact that glycol solutions or other heat transfer fluids will leak
where water will not, must be taken into account.
The glycol system should not employ an automatic fill with a pressure-reducing valve. This
is because a slight leak would lead to dilution of the mixture and possible freeze potential.
Any refill should be controlled so as to maintain the proper glycol-to-water ratio.
Table 2 shows pressure drops for various pipe sizes at flow rates commonly used with a
typical dry cooler. These pipe sizes are not necessarily always correct for the run from the
condenser to the dry cooler. Proper pipe size will depend on available pump head. This can
be determined by subtracting from the total available pump head at design flow, the
condenser pressure drop and the dry cooler pressure drop. Allow some safety factor for last
minute pipe fittings added to the system and for eventual fouling of the system.
a) Glycol piping requires no insulation except when fluid temperature will be below
b) Vents are required at all high points in the piping to bleed air when filling the system.
c) It is recommended that gate valves be installed on both sides of the pump to prevent
8
Table 1 provides weight of fluid per gallon. Provide suitable flashing of the roof, if this
is a roof installation. For ground level mounting, a concrete pad is recommended.
Mounting holes permit the units to be bolted down to withstand wind pressures.
Provide adequate clearance for unobstructed air flow to coils.
as flooded suction for the pump.
Table 1, Fluid Weight Per Gallon at 130
Percent Glycol
0 (Water)
10
20
30
40
50
pumping power and operating costs.
specific conditions on your job.
possible repair or replacement.
disconnecting provisions are provided.
ambient dewpoint temperatures.
If fluid coolers are at high points, vent valves should be installed at each fluid cooler.
loss of fluid in the event the pump should require repair or replacement. Shut-off
valves are also recommended at water cooled condensers in case the condensing unit is
to be moved or requires maintenance involving the coolant system.
Direct Drive Fluid Coolers
F
° ° ° °
Pounds per Gallon
Ethylene Glycol
8.25
8.33
8.50
8.58
8.80
8.82
Pounds per Gallon
Propylene Glycol
8.22
8.29
8.37
8.42
8.49
8.53
IOM 1062