Options; Distribution; Configurable Distribution (Cd) - Liebert UPStation S VM12000 User Manual

Liebert power protection user manual
Table of Contents

Advertisement

Contact your Liebert UPS distributor for option availability and ordering information.

Distribution

Configurable Distribution (CD)

An optional enclosure hardwires to 3.5 - 12 kVA units and accommodates up to eight Standard or Power Management Load
Modules. It may be wall or floor-mounted and includes a 70 Amp circuit breaker. Refer to drawings below.
2x4 Wall Stud
Wall Material (REF)
(REF)
Rack may be mounted 4" to the
right or left of location shown.
16"(REF)
TOP
VIEW
NOTES
Weight, including load modules, about 100 lbs.
Attach brackets to wall as shown using customer-
supplied 1/4" hex head lag screw or equivalent
hardware.
Options: 5' UPS to CD Power Cable, 5' Power
Management Power Cable, Wall Mount Bracket,
and Load Modules.
Refer to NEC Article 250 and local codes for proper
wire sizing and grounding practices.
Configurable Distribution may be used on all
Liebert UPStation S™ units up to 12 kVA.
BACK VIEW
19"
Rack Mat'l
¼ Washer
¼ Split Loc
¼ 20 Nut
Bracket
¼ 20x1.0
Bolt
Detail A

OPTIONS

TB2
L1
L2
N
TB1
N
L1
L2
Customer
Output
G
Communications Connector
8-12 kVA Rear View
16
This terminal
block allows for
daisy-chaining
of additional
distribution
units.
Power Management
Output
Terminal
Blocks
Output
Breaker
Output Terminal Block wire
range: (1) #14 - #2 AWG
per connection
Output Wiring
Access Area
Output Conduit
Landing Area
Input Conduit
Landing Area
RIGHT
SIDE
TB7
TB2
L1 L2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Upstation s vm18000Upstation s

Table of Contents