Grounding Configuration, Delta Source Or Impedance-Grounded Wye; Figure 5. Preferred Grounding Configuration With Delta Source Input - Liebert Series 600T Installation Manual

Liebert ups installation manual
Hide thumbs Also See for Series 600T:
Table of Contents

Advertisement

GROUNDING
ELECTRODE
PER NEC 250-24
GROUNDING
ELECTRODE
PER NEC 250-24
Figure 5. Preferred Grounding Configuration with Ungrounded Delta Source Input (top) and
7.5. Grounding Configuration, 480 or 600
VAC Input and Output, Delta Source
or Impedance-Grounded Wye
As previously mentioned, Series 600T UPS
modules require a bypass input neutral for sensing
and monitoring. With a wye-connected input
source, the installer should always connect the
building service neutral to the module output
neutral to achieve this. When the building service
is delta-connected, however, the installer must
take special steps to ensure reliable UPS
functioning.
12
LOCAL
GROUNDING
ELECTRODE
PER NEC 250-30
Corner-Grounded Delta (bottom)
If building service is ungrounded delta (and there
is no intent to operate with one corner of the delta
grounded, either on purpose or accidentally), the
UPS requires the Series 600T Artificial Neutral
Kit for proper operation. This kit uses a resistor
network to create a reference point for the bypass
input. In this case, the UPS output neutral must be
bonded to the UPS ground. See Figure 5 above.
If the building service is corner-grounded delta or
an impedance-grounded wye, the UPS requires the
Series 600T Isolated Neutral Kit. This kit uses
control isolation transformers to create a reference
point. For this application, the UPS output neutral
must not be bonded to the UPS ground.
LOCAL
GROUNDING
ELECTRODE
PER NEC 250-30
LOCAL
GROUNDING
ELECTRODE
PER NEC 250-30
Installation Manual

Advertisement

Table of Contents
loading

Table of Contents