Page 1
OWER VAILABILITY ™ Series 600T NSTALLATION ANUAL Multi-Module Three-Phase 65-225 kVA 60 Hz...
Page 2
FACTURER PRIOR TO MOVING A BATTERY CABINET. Battery cabinets contain non-spillable batteries. Keep units upright. Do not stack. Do not tilt. Failure to heed this warning could result in smoke, fire or electric hazard. Call 1-800-LIEBERT prior to moving battery cabinets.
AFETY RECAUTIONS I f t h e U P S s y s t e m h a s a b l o w n f u s e , t h e c a u s e s h o u l d b e d e t e r m i n e d b e f o r e y o u r e p l a c e t h e f u s e .
Figure 2 UPS Multi-Module Unit Block Diagram UPS MODULE Control Wiring To SCC CONTROL PO WER Controls Utility Output Rectifier/ Input Inverter Power Charger Power CB 1 To SCC Battery M BD M odule Input B reaker M odule Output Breaker MBD Module Battery D isconnect Types of System Control Cabinets Installation Considerations...
Page 17
Battery Safety Precautions in French Per CSA Requirements Instructions Importantes Concernant La Sécurité Conserver Ces Instructions Battery Installation...
ONFIGURING EUTRAL AND ROUND ONNECTIONS S o m e U P S m o d u l e s a r e e q u i p p e d w i t h i n p u t i s o l a t i o n t r a n s f o r m e r s . H o w e v e r , t h e s e t r a n s f o r m e r s h a v e n o e f f e c t u p o n a n y s y s t e m g r o u n d i n g c o n s i d e r a t i o n s .
Preferred Grounding Configuration, 480 or 600 VAC Input and Output, Isolated Power Distribution Units, Wye-Connected Service Figure 3 Preferred Grounding Configuration, 480 or 600 VAC Input and Output I m p e d a n c e - g r o u n d e d w y e s o u r c e s r e q u i r e a n I s o l a t e d N e u t r a l K i t i n a d d i t i o n t o t h e g r o u n d i n g a n d n e u t r a l c o n d u c t o r s s h o w n a b o v e .
Grounding Configuration, 480 or 600 VAC Input and Output, Delta Source Figure 4 Grounding Configuration with Ungrounded Delta Source Input u n g r o u n d e d d e l t a m u s t c o r n e r - g r o u n d e d d e l t a I m p e d a n c e - g r o u n d e d w y e m u s t n o t T h e A r t i f i c i a l N e u t r a l K i t i n t r o d u c e s a m a x i m u m c u r r e n t o f 0 .
Preferred Grounding Configuration with Power-Tie Switchgear Figure 5 Preferred Grounding Configuration, Power-Tie Systems n o t I t i s e s s e n t i a l t o r u n a n e u t r a l c o n n e c t i o n b e t w e e n t h e t i e s w i t c h g e a r a n d b o t h S C C s a s s h o w n i n t h e i l l u s t r a t i o n a b o v e .
IRING ONNECTIONS M a k e s u r e a l l r e q u i r e d w i r i n g b e t w e e n e a c h U P S m o d u l e a n d t h e o p t i o n a l c a b i n e t ( s ) i s c o m p l e t e d .
Page 31
Abbreviations for Circuit Breakers Bypass Feeder Breaker Bypass Input Breaker Module Input Breaker Module Output Breaker Maintenance Bypass Breaker Module Battery Disconnect MBFB Maintenance Bypass Feeder Breaker Maintenance Isolation Breaker Rectifier Input Breaker System Bypass Breaker Static Bypass Switch D C p o w e r a n d b a t t e r y c i r c u i t b r e a k e r c o n t r o l c a b l e s a r e p r o v i d e d w i t h s o m e L i e b e r t - b r a n d B a t t e r y C a b i n e t s .
10.0 W IRING NSPECTION Table 1 Power Wiring Terminals - Factory Supplied UPS Module Rating Connection Type 65 & 80 kVA Rectifier input is top entry, to lugs in the top of the input circuit breaker. Lugs will accommodate cabling up to 350MCM. DC link and critical bus output connections are top entry, to frame-mounted terminal blocks with one 3/8- 16x1 stud per phase or polarity.
Page 33
Table 3 Table 310-16 Allowable Ampacities of Insulated Conductors Rated 0-2000 Volts, 60° to 90°C (140° to 194°F) Not More than Three Conductors in Raceway or Cable or Earth (Directly Buried), based on Ambient Temperature of 30° (86°F) Size Temperature Rating of Conductor. See Table 310-13. Size 60°C 75°C...
12.0 A A - S PPENDIX LANNING 65-225 kVA Multi-Module Systems 12.1 Notes Appendix A - Site Planning Data...
Page 83
Table 4 Series 600T Multi-Module Systems, 65-225 kVA - 208 Volt Input Required Maximum Rectifier Battery Battery Maximum Floor Inverter Discon- Current Heat Dis- Dimen- Approx. Loading Input AC Output nect at End of sipation sions Weight Lb./ Rating Options Current Current Rating...
Page 84
Table 5 Series 600T Multi-Module Systems, 65-225 kVA - 480 Volt Input Inverter Required Maximum Rectifier Battery Battery Maximum Floor Bypass Discon- Current Heat Dis- Dimen- Approx. Loading Input AC Output nect at End of sipation sions Weight Lb./ Rating Options Current Current...
Page 85
Table 6 Series 600T Multi-Module Systems, 65-225 kVA - 600 Volt Input Inverter Required Maximum Rectifier Battery Battery Maximum Floor Bypass Discon- Current Heat Dis- Dimen- Approx. Loading Input AC Output nect at End of sipation sions Weight Lb./ Rating Options Current Current...
The Company Behind the Products United States With over a million installations around the globe, 1050 Dearborn Drive Liebert is the world leader in computer protection P.O. Box 29186 systems. Since its founding in 1965, Liebert has Columbus, OH 43229...