Table 5 Battery Run Times - Liebert PowerSure PSI 1000 - 3000VA 60 Hz 120V User Manual

Liebert corporation user manual power supply 1000 - 3000va, 60 hz, 120v
Table of Contents

Advertisement

Table 5
Battery run times
Internal Battery
(minutes)
Internal Battery
+ 1 External
Battery Cabinet
(minutes)
Internal Battery
+ 2 External
Battery Cabinets
(minutes)
Internal Battery
+ 3 External
Battery Cabinets
(minutes)
Internal Battery
+ 4 External
Battery Cabinets
(minutes)
NOTE
Approximate discharge times are in minutes and at 77°F (25°C) with resistive load.
Load%
1000VA
5%
174
10%
118
20%
65
30%
41
40%
37
50%
26
60%
24
70%
18
80%
16
90%
12
100%
11
5%
513
10%
305
20%
248
30%
177
40%
139
50%
119
60%
98
70%
75
80%
63
90%
53
100%
46
5%
1001
10%
565
20%
409
30%
283
40%
248
50%
209
60%
166
70%
136
80%
127
90%
110
100%
98
5%
1174
10%
1001
20%
565
30%
409
40%
305
50%
274
60%
248
70%
209
80%
188
90%
145
100%
136
5%
1174
10%
1174
20%
828
30%
513
40%
461
50%
305
60%
283
70%
257
80%
239
90%
209
100%
188
1440VA
1920VA
138
181
79
104
45
52
28
31
24
25
16
19
14
15
10
11
9
10
6
8
5
6
409
575
265
294
188
208
125
143
104
123
72
105
59
82
45
59
40
53
35
47
30
43
828
461
590
283
307
219
243
177
197
133
163
122
141
98
128
84
115
64
102
56
89
1001
655
409
522
283
298
257
267
209
237
166
197
136
166
125
147
110
138
95
128
828
565
639
357
458
292
322
257
281
230
252
188
220
156
192
136
169
125
150
28
Specifications
2200VA
3000VA
171
177
73
91
47
47
26
28
23
22
16
16
13
14
10
10
8
9
6
7
5
6
542
542
266
257
185
148
135
141
122
99
99
67
75
53
55
45
49
39
44
34
40
29
493
444
291
249
222
168
194
148
150
129
137
114
122
92
107
71
92
56
77
52
590
493
300
283
240
266
213
222
168
185
144
156
129
141
116
131
101
120
88
590
444
395
283
300
266
274
222
240
179
203
150
173
139
156
129
144
118

Hide quick links: