Installation; Preparation; Tower Ups Installation - Liebert GXT 2U User Manual

Liebert power availability upstation user manual gxt 2u
Hide thumbs Also See for GXT 2U:
Table of Contents

Advertisement

4.0
I
NSTALLATION
4.1
P
REPARATION
1. Visually inspect the UPS for freight damage. Report damage to
the carrier and your local dealer or Liebert representative.
CAUTION
!
The UPS is heavy (see 11.0 - Specifications). Take proper
precautions when lifting or moving it.
2. Decide where to place the GXT 2U. Install the UPS indoors in a
controlled environment, where it cannot be accidentally turned off.
Place it in an area of unrestricted airflow around the unit, away
from water, flammable liquids, gases, corrosives, and conductive
contaminants. Maintain a minimum clearance of 4 in. (100mm) in
the front and rear of the UPS. Maintain an ambient temperature
range of 32°F to 104°F (0°C to 40°C).
NOTE
UPS operation in temperatures above 77°F (25°C) reduces
battery life.
3. The GXT 2U may be installed in either a tower configuration or in
a rack, depending on available space and use considerations.
Determine the type of installation and follow the appropriate
instructions in either 4.2 - Tower UPS Installation or 4.3 -
Rack-Mount UPS Conversion and Installation.
4.2
T
OWER
When using the GXT 2U in a tower configuration, use the included
support base (shown below, left) to stabilize the UPS.
If any battery cabinets are added, they will include spacers to accom-
modate the additional cabinets (shown below, right).
Support base
UPS I
NSTALLATION
Spacers added to support
base to accommodate
additional battery cabinets
8

Installation