Daikin Altherma Installer's Reference Manual page 65

Low temperature split
Hide thumbs Also See for Altherma:
Table of Contents

Advertisement

INFORMATION
If the power saving function is activated (see [E‑08]), the
average outdoor temperature calculation is only possible in
case the external outdoor temperature sensor is used. See
"5.7 Setting up an external temperature sensor" on
page 21.
Offset temperature external outdoor ambient sensor
Only applicable in case of an external outdoor ambient sensor is
installed and configured.
You can calibrate the external outdoor ambient temperature sensor.
It is possible to give an offset to the thermistor value. The setting can
be used to compensate for situations where the external outdoor
ambient sensor cannot be installed on the ideal installation location
(see installation).
#
Code
[A.6.5]
[2-0B]
−5~5°C, step 0.5°C (default: 0°C)
Forced defrost
You can manually start a defrost operation.
The decision to execute the manual defrost operation is made by the
outdoor unit and depends on ambient and heat exchanger
conditions. When the outdoor unit accepted the forced defrost
operation,
will be displayed on the user interface. If
displayed within 6 minutes after forced defrost operation was
enabled, the outdoor unit ignored the forced defrost request.
#
Code
[A.6.6]
N/A
Do you want to start a defrost operation?
▪ OK
▪ Cancel
Pump operation
The pump operation field setting apply to the pump operation logic
only when [F-0D]=1.
When the pump operation function is disabled the pump will stop if
the outdoor temperature is higher than the value set by [4-02] or if
the outdoor temperature drops below the value set by [F-01]. When
the pump operation is enabled, the pump operation is possible at all
outdoor temperatures.
#
Code
N/A
[F-00]
Pump operation:
▪ 0: Disabled if outdoor temperature is
higher than [4-02] or lower than [F-01]
depending
operation mode.
▪ 1:
temperatures.
Pump operation during flow abnormality [F-09] defines whether the
pump stops at flow abnormality or allow to continue operation when
flow abnormality occurs. This functionality is only valid in specific
conditions where it is preferable to keep the pump active when
T
<4°C (pump will be activated for 10 minutes and disactivated after
a
10 minutes). Daikin shall NOT be held liable for any damage
resulting this functionality.
#
Code
N/A
[F-09]
Pump continue operation when flow
abnormality:
▪ 0: Pump will be desactivated.
▪ 1: Pump will be activated when
T
a
OFF)
ERLQ004~008CAV3 + EHBH/X04+08CA
Daikin Altherma - Low Temperature Split
4P313774-1C – 2012.11
Description
is NOT
Description
Description
on
heating/cooling
Possible
at
all
outdoor
Description
<4°C (10 minutes ON – 10 minutes
8 Configuration
Installer reference guide
65