Table 24 Dehumidification Troubleshooting; Table 25 Glycol Pump Troubleshooting; Table 26 Infrared Humidifier Troubleshooting - Liebert CHALLENGER 3000 Operation And Maintenance Manual

3 & 5 ton, 50 & 60hz
Hide thumbs Also See for CHALLENGER 3000:
Table of Contents

Advertisement

Table 24
Dehumidification troubleshooting
Symptom
No dehumidification
Table 25
Glycol pump troubleshooting
Symptom
Suddenly stops pumping
Suddenly slow pumping
Excessive leakage around the pump
shaft while operating
Performance poor
Noisy operation
Table 26
Infrared humidifier troubleshooting
Symptom
No humidification
Possible Cause
Control not calling for
dehumidification
Compressor contactor not pulling in
Compressor won't run; fuse blown or
CB tripped
Possible Cause
Clogged strainer or impeller
Clogged impeller, diffuser, or line
Worn seal or packing
Worn impeller or seal
Suction lift too high
Motor not up to speed; low voltage
Worn bearings
Worn motor bearings
Low discharge head
Debris lodged in impeller
Cavitating pumps
Possible Cause
Humidifier pan not filling
Control not calling for humidity
Humidity contact not pulling in
Humidifier bulb burned out
61
Troubleshooting
Check or Remedy
Check monitor status.
See 6.4.8 - Compressor Functional
Check and Table 23.
See 6.4.8 - Compressor Functional
Check and Table 23. Check fuses or
CBs and contacts. Check line voltage
Check or Remedy
Clean out debris.
Clean out debris and use strainer.
Replace seal or packing.
Replace with new impeller or seal.
Relocate pump closer to supply.
Larger lead wires may be required.
Check for proper line voltage (±10%).
Replace pump
Replace pump
Throttle discharge-improve suction
conditions.
Remove cover and clean out.
Adjust system pressures.
Check or Remedy
Check water supply.
Check fill valve operation
Check drain stand pipe adjustment
Check for clogged waterline
Check monitor status
Check visually. If contact is made,
check line voltage after contactor and
fuses or CBs.
Check for open humidifier safety stat.
Jumper between terminals P35-6 and
P35-15. If contactor pulls in, replace
safety. Remove jumper.
Replace bulb. Loosen lead on old
bulb. Trim excess lead length on new
bulb to avoid shorts.