FUNCTIONAL SPECIFICATIONS ACP BACnet
Remarks
• StartStopStatus_XXX
1. If there is an operation error, the Present_Value property will be set to ACTIVE regardless of
whether the A/C is in operation or not.
• FilterSign_XXX
1. This object supports the Intrinsic Reporting function. When the Present_Value property changes,
the corresponding Event will be transmitted if the Event has been registered.
• StartStopCommand_XXX
1. The command executed is transmitted to the A/C regardless of the status of the A/C.
2. Present_Value property will not be used if a property has never been set in the past.
• FilterSignReset_XXX
1. During a read operation of the Present_Value property, the Fliter Limit Sign Reset will be always
the same value as the Filter Limit Sign object.
2. Only if INACTIVE is written to the Present_Value property during a write operation, the filter sign
information resets ON signs and nothing will be executed even if ACTIVE is written.
3. This object supports the Intrinsic Reporting function. When the Present_Value property changes,
the corresponding Event will be transmitted if the Event has been registered.
• FanSpeedStatus_XXX
1. Present_value property will be set to "1:Low" as the default result if the property has not been set
in the past.
• UserModeStatus_XXX
1. This object is for vent only, and will not apply if the property has not been in the past.
• MalfunctionCode_XXX
1. This object's error code descriptions should be referred to the corresponding table at the
"Reference LG original Error Code".