40
INSTALLING ACP BACnet
2.
Insert USB memory or SD card into the ACP BACnet. (Refer to software update and data
backup)
3.
Press [SET] button of the ACP BACnet.
4.
Select [Function] menu, and press [SET] button.
5.
Select [DB recover] menu, and press [SET] button again.
6.
Select [USB] or [SD card], and press [SET] button.
7.
Remove USB memory after completing the data recovery.
• ACP BACnet is automatically restarted for data recovery.
Caution
Before data recovery is completed, turning off the power of the ACP BACnet or removing USB
memory or SD card may cause severe disorder of the ACP BACnet.
PQNFB17C0
Automatic restart
of ACP BACnet
Network Info
Contents
>
Function
Register FD
Click
[SET]
button
[Function 1/2]
S/W update
DB back up
>
DB recover
Click
[SET]
button
>
USB
SD card
Click
[SET]
button
Remove USB
Auto Restart
[DB recover]
[Completed]
or SD card
[Completed]