Vertical Into Existing Class A Chimney; Through The Wall & Vertical - Exterior; Vertical - Interior - Typical Installation - Quadra-Fire MTVERNON-AE-CSB Installation Manual

Installation & appliance set-up
Hide thumbs Also See for MTVERNON-AE-CSB:
Table of Contents

Advertisement

C. Vertical into Existing Class A Chimney
Flashing
Firestop
Ceiling Support
6 in.
(152mm)
Min.
Non-combustible Hearth Pad
Figure 15.1
D. Through The Wall & Vertical - Exterior
2 in. (51mm) minimum
6 in. (152mm)
minimum
Figure 15.2
May 5, 2015
Rain Cap
12 in. (305mm) Minimum
6 in. (152mm) Class A
Chimney Connector
Adapter
3 in. (76mm) Min.
3 to 3 in.
(76-76mm)
Top Vent Kit
Clean-out Cover
Rain
Cap
12 in.
Flashing
(305mm)
minimum
Support
Bracket
every 60 in.
(1524mm)
Wall Thimble
Tee
Clean-out
Cover
Non-combustible Hearth Pad
We recommend a minimum of 60 inches
(1524mm) vertical, however above the eave
is preferred.
All three installations are approved for mobile
home installations. Must use 3 or 4 inch (76
to 102mm) "L" or "PL" Listed pellet venting or
Listed double wall pipe and Quadra-Fire Outside
Air Kit in mobile homes. Single wall pipe is
approved for residential installations only.
*NOTE: Clearance to combustibles are for
standard pellet pipe. If pellet pipe manufacturer
allows reduced clearances to their pipe, reduced
clearances are allowed.
3 to 6 in. (76-152mm)
Offset Adapter
A chimney connector shall not pass through
an attic or roof space, closet or similar
concealed space, or a fl oor or ceiling.
E. Vertical - Interior - Typical Installation
6 in.
(152mm)
Min.
Non-combustible Hearth Pad
Figure 15.3
7034-277E
MT. VERNON AE
NOTE:
Rain Cap
12 in.
Flashing
(305mm)
Minimum
Firestop
3 in. (76mm) Min.
3 in. to 3 in.
(76-76mm)
Top Vent Kit
Clean-out Cover
15