Specification - Wolf MGK-130 Technical Manual And Installation Instructions

Gas condensing boilers
Table of Contents

Advertisement

Type
Rated output at 80/60 °C
Rated output at 50/30 °C
Rated heat input
Low boiler output (modul.) at 80/60 °C
Low boiler output (modul.) at 50/30 °C
Low heat input (modulating)
Heat input modulation range
Height
Width
Depth
Flue diameter
Combustion air supply
Heating flow outside diameter
Heating return outside diameter
Gas connection
Balanced flue routing
Gas category
Gas supply details:
Natural gas H (H
= 9.5 kWh/m³ = 34.2 MJ/m³)
i
LPG P (H
= 12.8 kWh/kg = 46.1 MJ/kg)
i
Gas supply pressure: Natural gas E/LL
LPG P
Water capacity, heating water heat exchanger
Max. permissible boiler pressure
Max. permissible flow temperature
Available gas fan draught
Flue gas temperature 80/60-50/30 at Q
Flue gas temperature 80/60-50/30 at Q
Flue gas mass flow rate
Flue gas group according to DVGW G 635
Pressure drop, heating water
Electrical connection
Integral fuse (medium slow)
Power consumption
Protection
Sound pressure level inside the installation
room at full load
1)
Total weight (dry)
Condensate volume at 40/30 °C
Condensate pH value
CE ID
This value is dependent on the general system conditions, such as: Type/version of the flue system, size and nature of the installation room
1)
6

Specification

MGK
130
kW
117
kW
126
kW
120
kW
23
kW
24
kW
23
%
19-100
A mm
1300
B mm
995
C mm
600
mm
160
mm
160
G
1½"
G
1½"
R
1"
B23, B33
C33, C43
Type
C53, C63
C83
II
2H3P
m³/h
13.1
kg/h
9.7
1)
mbar
20
mbar
50
l
12
bar
6
°C
90
Pa
10-200
°C
65-45
max
°C
55-35
min
g/s
56.7
G52
mbar
95
V~/Hz
230/50
A
5
W
30-200
IP40D
dB(A)
<54
kg
195
l/h
12
approx. 4.0
0085BR0117
170
210
156
194
167
208
160
200
27
34
30
37
28
35
17-100
17-100
1300
1300
1355
1355
600
600
160
160
160
160
2"
2"
2"
2"
1½"
1½"
B23, B33
B23, B33
C33, C43
C33, C43
C53, C63
C53, C63
C83
C83
II
II
2H3P
2H3P
16.8
21
12.5
15.6
20
20
50
50
15.4
16
6
6
90
90
10-150
10-150
65-45
65-45
55-35
55-35
72.6
90.8
G52
G52
100
115
230/50
230/50
5
5
45-280
45-280
IP40D
IP40D
<54
<54
250
271
16
20
approx. 4.0
approx. 4.0
0063BQ3805
0063BQ3805
250
300
233
275
250
294
240
280
39
45
44
49
41
46
17-100
17-100
1300
1300
1355
1355
600
600
160
200
160
160
2"
2"
2"
2"
1½"
1½"
B23, B33
B23, B33
C33, C43
C33, C43
C53, C63
C53, C63
C83
C83
II
II
2H3P
2H3P
25.2
29.4
18.7
21.8
20
20
50
50
20
22
6
6
90
90
10-150
10-150
65-45
65-45
55-35
55-35
108.9
127.1
G52
G52
135
160
230/50
230/50
5
5
45-280
45-280
IP40D
IP40D
<54
<54
292
313
24
28
approx. 4.0
approx. 4.0
0063BQ3805
0063BQ3805
3062880_0910

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mgk-170Mgk-250Mgk-300Mgk-210