MGK-2 heating water pressure drop:
Max. spread
Flow rate
8

4. Specification

Throughput [m³/h]
A cast section protection function is integrated in the MGK-2. This prevents stresses in
the material by limiting the maximum temperature differential between the flow and
return. As of 28 K, the output is reduced. If 40 K is nevertheless reached, the burner
shuts down briefly without a fault message. This characteristic must be taken into account
when selecting the components (e.g. pumps, heat exchanger and cylinder).
Excessive flow velocities may lead to erosion.
Maximum flow rate (volume flow) at Q
MGK-2-390: 28.5 m³/h
MGK-2-470: 34.4 m³/h
MGK-2-550: 39.8 m³/h
MGK-2-630: 45.5 m³/h
:
max
3063772_201507