Adjusting the gas / air connection
Carry out the adjustments in the following
NB
sequence: At the factory, the gas combination
valve has been set up for natural gas E (G20).
Only adjust the gas combination valve after
the system has been changed to a different
gas type.
Converting the MGK-130 to LPG P
A separate conversion kit with gas restrictor, gas
combination valve and boiler coding card is required
for this conversion. Observe the information in the
conversion instructions supplied.
Conversion MGK-170/210/250/300 to P
A separate conversion kit with boiler coding card is
required for this conversion. Observe the information
in the conversion instructions supplied.
Conversion kits MGK LPG
Type
MGK-130
MGK-170 and MGK-250
MGK-210
MGK-300
Overview boiler coding cards MGK
Type
Part no.
boiler coding card
for natural gas H
MGK-130
27 44 358
MGK-170
27 44 238
MGK-210
27 44 237
MGK-250
27 44 170
MGK-300
27 44 359
3062880_0910
Changing the gas type / CO
Part no. conversion kit
87 51 351
87 51 293
87 51 295
87 51 298
Part no.
boiler coding card
for LPG P
27 44 356
27 44 354
27 44 355
27 44 354
27 44 357
A standard adjustment at the GCV is always required
for a change of gas type to be effective.
Make the standard settings at the gas combination
valve in accordance with the table. Otherwise there
is a risk of damage to the appliance.
Carefully turn the screw fully home and then undo as
follows:
Standard setting for different gas types: Turn anti-
clockwise
Natural gas H
Type
Zero point
adjusting screw
MGK-130
1 ¾ turns
Natural gas H
Type
Zero point
adjusting screw
MGK-170
2 turns
MGK-210
1 ½ turns
MGK-250
1 ½ turns
MGK-300
1 ¾ turns
For other standard settings relating to the gas
type, see the conversion instructions.
settings
2
Gas restrictor 1000
Throughput
adjusting screw
1 ½ turns
1 ¾ turns
1 ¾ turns
2 turns
27