Max. spread
Max. flow rate
Pump sizing MGK
130/170/210/250/300
34

Engineering data

A cast section protection function is integrated in the MGK. This prevents
stresses in the material by limiting the maximum temperature differential
between the flow and return. As of 28 K, the output is reduced. If 38 K is
nevertheless reached, the burner shuts down briefly without a fault message.
This characteristic must be taken into account when selecting the components
(e.g. pumps, heat exchanger and cylinder).
Excessive flow velocities may lead to erosion.
Maximum flow rate at Q
The following Wilo and Grundfos pumps represent recommendations in
conjunction with the installation of a MGK with a low loss header.
Select pumps in accordance with the respective system if no low loss header
is to be installed.
MGK
Type
130
Wilo-Top-S
Grundfos UPS 32 - 30 F
170
Wilo-Top-S
Grundfos UPS 32 - 30 F
210
Wilo-Top-S
Grundfos UPS 40 - 30 F
250
Wilo-Top-S
Grundfos UPS 40 - 30 F
300
Wilo-Top-S
Grundfos UPS 50 - 30 F
Throughput [m³/h]
:
MGK-130
max
MGK-170
MGK-210
MGK-250
MGK-300
Version
Connection type
25/7 and 30/7 230 V - Rp1 / Rp¼ threaded fittings
230 V - Rp¼ threaded fittings
25/7 and 30/7 230 V - Rp1 / Rp¼ threaded fittings
230 V - Rp¼ threaded fittings
30/4
230 V - Rp¼ threaded fittings
230 V - DN 40 flange fitting
40/4
230 V - DN 40 flange fitting
230 V - DN 40 flange fitting
40/4
230 V - DN 40 flange fitting
230 V - DN 40 flange fitting
9.4 m³/h
13.6 m³/h
16.4 m³/h
19.1 m³/h
21.9 m³/h