Condensate connection
Fill the siphon with water prior to commissioning.
Otherwise there is a risk of flue gas escaping.
When routing condensate into the public sewer system,
observe local regulations. If condensate is directly routed
to the public sewer, ensure ventilation, so that the public
sewer cannot affect the condensing boiler.
Use only plastic for all condensate drain
NB
pipes.
Neutralising system (accessory)
The neutralising system can be connected directly to the
appliance. Consumption approx. 10-30 g/kW p.a.
Observe the associated instructions.
Trim the connection hoses, so that
NB
- the condensate can drain fully
- backup loops are prevented
- a perfect seal is ensured.
Condensate drain, single boiler systems
When installing the MGK as an individual appliance, fit a
condensate drain (DN 160 - part no. 2651341, DN 200
- part no. 2651389).
The connections of the condensate source can be joined
with the "Condensate hose set" (part no.8905844) and
can be connected to the neutralising system.
3062880_0910
Installation
Fig.: Siphon
Fig.: Neutralising system (accessory)
Fig.: Condensate hose
Siphon