General tips regarding location
• The boiler should be installed on a level surface which
is substantial enough to carry its weight.
• The boiler must be level (level with adjustable feet).
The boiler must only be installed in a room that
NB
is protected from frost.
Drain the boiler and the entire heating system if
there is a risk of frost, when the system has been
shut down, to prevent pipes from bursting.
Boilers should not be installed in areas subject
NB
to aggressive vapours, very dusty or highly
humid conditions (workshops, laundry rooms,
hobby rooms etc.). This prevents the optimum
burner function from being achieved.
The combustion air supplied to the boiler must
be free from halogenated hydrocarbons (e.g.
as contained in sprays, solvents, cleaning
fluids, paints and adhesives). Under the most
unfavourable conditions, these may lead to
pitting of the boiler and even the flue gas
system.
Never store or use combustible material or
liquids near the boiler.
The ventilation air supply must be ensured
and comply with local regulations or those
relating to gas installations. When there is
an insufficient supply of ventilation air, flue
gas can escape leading to a risk to life
(poisoning/asphyxiation).
Prior to commissioning, ensure with the
appropriate authorities, whether a neutralising
system for condensate is required.
Recommended minimum wall clearances
The boiler can be positioned close to the wall, both at
its back and its left side.
On the right side, a clearance of at least 500 mm is
required to enable the burner removal and installation.
An adequate amount of space must also be provided in
front of the boiler to enable cleaning and service.
10
Installation instructions
Dim. B
MGK-130
Dim. B
MGK-170/210/250/300 1355 mm
Boiler in the installation room
2 - 4 boilers in the installation room, side by side
2 boilers in the installation room
2 boilers in the installation room, back to back
995 mm
3062880_0910