3.10. BOILER LOCATION AND VENTILATION
3.10.1. Boiler Location
The boiler may be installed in any room although particular attention is drawn to the requirements of the
current issue of BS7671 with respect to the installation of a boiler in a room containing a bath or a shower.
Any electrical switch or boiler control using mains electricity supply should be so sited that a person using the
bath or a shower cannot touch it. The electrical provisions of the Building Standards (Scotland) Regulations
are applicable to such installations in Scotland.
These boilers are not suitable for fitting outdoors. The boiler must be mounted on a flat wall, which is
sufficiently robust to take its total weight given in table 3.1.
3.10.2. Clearances
The boiler should be positioned and installed so that at least minimum clearances shown in diagram 3.10,
required for servicing and correct operation are provided. Additional clearances may be useful around the
boiler for installation and servicing.
For flue installations where external access is not practical, considerations should be given for the space
required to insert the flue internally, which may require clearances larger than those specified in diagram
3.10.
220
220
20
20
200
200
VER: 02.3 _260505
Supplied By www.heating spares.co Tel. 0161 620 6677
5*
5*
5*
5*
5*
20
20
All dimensions in mm
All dimensions in mm
* Increase to 25mm clearances from combustible surfaces
* Increase to 25mm clearances from combustible surfaces
Diagram 3.10 Minimum clearances from
Diagram 3.10 Minimum clearances from
permanent fixed surfaces
permanent fixed surfaces
5*
5*
5*
Flue
Flue
Flue
Front
Front
Front
600
600
600