VISTA-50P/VISTA-50PUL Installation and Setup Guide
FIELD
TITLE and DATA ENTRIES

Primary Phone Number

*33
Enter 0-9; #11 for *, #12 for #, #13 for a 2-
second pause.

Secondary Phone Number

*34
Enter 0-9; #11 for *, #12 for #, #13 for a 2-
second pause.

Download Phone Number

*35
Enter 0-9; #11 for *, #12 for #, #13 for a 2-
second pause.

Download ID Number

*36
Make entries as 2-digit numbers as follows:
00=0 01=1
06=6 07=7
12=C 13=D 14=E 15=F

Download Command Enables

*37
0 = disable
1 = enable

Prevent Zone XX Bypass

*38
(partition-specific)
Enter a zone number (01-86).
Enter 00 if all zones (except fire zones) can
be bypassed.
Enable Open/Close Report for
*39
Installer Code (partition-specific)
0 = disable
1 = enable
Enable Open/Close report for
*40
Keyswitch
0 = disable
1 = enable
Normally Closed or EOLR (Zones
*41
2-8)
0 = disable
1 = enable

Dial Tone Pause

*42
Enter the wait time for dial tone detection:
0 = 5 seconds; 1 = 11 seconds; 2 = 30
seconds.
5-4
02=2
03=3
04=4
05=5
08=8
09=9
10=A 11=B
WWW.DIYALARMFORUM.COM
EXPLANATION
Enter the primary central station phone number, up to 17 digits. This is
the phone number the control will use to transmit Alarm and status
messages to the central station. Do not fill unused spaces.
NOTE: Backup reporting is automatic only if a secondary phone number
is entered.
Enter the secondary phone number, up to 17 digits. The secondary phone
number is used if communication on the primary number is unsuccessful,
or if split/dual reporting is desired. Do not fill unused spaces.
NOTE: If this field is programmed, a secondary subscriber account
number (field *90) must also be programmed.
Enter the downloading phone number, up to 17 digits. Do not fill unused
spaces.
NOTE: This field is applicable only if downloading is utilized.
Enter eight digits.
NOTE: This field is applicable only if downloading is utilized.
Enabling a function means that you are able to perform that function via
the Compass Downloading software.
Functions are as follows: Dialer Shutdown; System Shutdown; Not Used;
Remote Bypass; Remote Disarm; Remote Arm; Upload Program;
Download Program.
For UL installations, all entries must be 0.
Enter two digits for zone that cannot be bypassed by the user.
NOTES:
The actions manual bypass, and STAY/INSTANT arming modes cannot
bypass any zone programmed in this field.
If enabled, whenever the Installer Code is used to arm or disarm the
partition, an open/close report is sent to the central station.
If enabled, whenever the keyswitch is used to arm or disarm the partition,
an open/close report is sent to the central station.
If disabled, end-of-line resistors must be used on zones 2-8.
If enabled end-of-line resistors cannot be used and only normally closed
devices must be used.
Must be 0 for UL installations.
Enter the time the system waits for dial tone before dialing. Applies if
true dial tone is not selected in field *43.
Must be 0 for UL installations.