[5] Function of Dip SW and Rotary SW

(1) Outdoor unit
Switch
Function
SWU
1~2
Unit address setting
SW1
1~8
For self diagnosis/
operation monitoring
9~10
SW2
1
Centralized control switch
2
Deletion of connection
information.
3
Deletion of error history.
4
5
6
Disregard ambient air
sensor errors, liquid
overflow errors.
7
Forced defrosting
8
Defrost prohibited timer
9
10
SW3
1
SW3-2 Function valid/
invalid
2
Indoor unit test operation
3
Defrosting start tempera-
ture of TH7.
4
Defrosting end tempera-
ture of TH5.
5
6
Pump down operation
7
Target Td (High pressure)
at Heating
8
9
10
Models
SW4
1
2
3
4
5
LED Display
6
7
8
9
10
Note:
• SWU1~2=00 when shipped from the factory. Other factory settings are indicated by shaded portions.
• If the address is set from 01 to 50, it automatically becomes 100.
Function according to switch operation
When off
Set on 51~100 with the dial switch.
LED monitering display
Centralized control not
Centralized control
connected.
connected.
Storing of refrigeration
Deletion of refrigeration
system connection
system connection
information.
information.
Deletion
Errors valid.
Disregard errors.
Ordinary control
Start forced defrosting.
50 min.
SW3-2 Function invalid
SW3-2 Function valid
Stop all indoor units.
All indoor units test
operation ON.
–6°C
(21˚F)
8°C
(46˚F)
Invalid
49˚C
(120˚F)
Model 80
"˚F" "psig" Display
–20–
When on
Before power is turned on.
During normal operation when power
is on.
Should be set on OFF.
Before power is turned on.
Before power is turned on.
During normal operation when power
is on.
During normal operation when power
is on.
During normal
operation when
power is on.
90 min.
During normal operation when power
is on. (Except during defrosting)
During normal operation when power
is on.
When SW3-1 is ON after power is
turned on.
–3°C
During normal operation when power
(27˚F)
is on.
15°C
During normal operation when power
(59˚F)
is on. (Except during defrosting)
Valid
During compressor stop when power
is on.
53˚C
During normal operation when power
(127˚F)
is on.
Model 100
When switching on the power.
"˚C" "kgf/amG" Display
Switch set timing
When off
When on
10 minutes or
more after
compressor
starts.
When switching on the power