Mitsubishi Electric PURY-80TMU Service Handbook page 59

City multi
Table of Contents

Advertisement

Outdoor LEV (SLEV) Coil Removal Procedure (configuration)
As shown in the figure, the outdoor LEV is made in such a way that the coils and the body can be separated.
<Removing the Coils>
Fasten the body tightly at the bottom (Part A in the figure) so
that the body will not move, then pull out the coils toward the
top. If they catch on the stopper and are difficult to take out,
turn the coils left and right until the stoppers are free from the
stopper indentations, then pull the coils out.
If you take out the coils only without gripping the body, undue
force will be applied to the piping and the pipe may be bent
over, so be sure to fasten the body in such a way that it will not
move.
Coils
Stopper
Lead Wires
Part A
–58–