Function Of Dip Sw And Rotary Sw - Mitsubishi Electric CITY MULTI PQRY-P200YMF-B Service Handbook

Air conditioners city multi
Table of Contents

Advertisement

[6] Function of Dip SW and Rotary SW

(1) Heat source unit
Switch
Function
SWU
1~2
Unit address setting
SW1
1~8
For self diagnosis/
operation monitoring
9~10
SW2
1
Centralized control switch
2
Deletion of connection
information.
3
Deletion of error history.
4
Adjustment of refrigerant
Volume
5
6
7
Operation ON signal
output switching
Relay contact output
TB8-1,2
8
Disregard pump interlock
trouble.
9
10
SW3
SW3-2 Function valid/
1
invalid
Indoor unit test operation
2
CN51-3,5 Output switching
3
Freeze prevention operation
4
Target Te (α) at cooling-
5
only
Pump down operation
6
Target Tc (High pressure)
7
at heating
8
9
10
Models
SW4
1
SW4-2 function valid/
Invalid
2
Configuration compensa-
tion value
3
Note:
• SWU1~2=00 when shipped from the factory. Other factory settings are indicated by shaded portions.
• If the address is set from 01 to 50, it automatically becomes 100.
* Freeze prevention operation
When the water temp. (TH6) below less 5˚C during compressor is stopping, the compressor starts to run with cooling mode to
prevent the water freeze.
Function according to switch operation
When off
Set on 51~100 with the dial switch.
LED monitering display
Centralized control not
Centralized control
connected.
connected.
Storing of refrigeration
Deletion of refrigeration
system connection
system connection
information.
information.
Deletion
Ordinary control
Refrigerant volume
adjustment operation.
The relay closes during
The relay closes during
compressor operation.
reception of the cooling or
the heating operation
signal from the controller.
(Note: It is output even if
the thermostat is OFF
(when the compressor is
stopped).)
Normal
Disregard trouble
SW3-2 Function invalid
SW3-2 Function valid
Stop all indoor units.
All indoor units test
operation ON.
Water heat exchanger
Heat source unit abnormal
freeze prevention signal
output
Normal
Freeze prevention operation*
–2˚C
Invalid
50˚C
Model P200
Invalid
Changes as shown below by on → off change
0% → 3% → 6% → 9% → 12% → –6% → –3% → 0%
–29–
When on
When off
Before power is turned on.
During normal operation when power
is on.
Should be set on OFF.
Before power is turned on.
Before power is turned on.
During normal operation when power
is on.
During normal
operation when
power is on.
At all times
At all times
During normal operation when power
is on.
When SW3-1 is ON after power is
turned on.
At all times
At all times
–5˚C
At all times
Valid
During Comp stop (only when power
changes from OFF → ON)
53˚C
During normal operation when power
is on.
Model P250
When switching on the power.
Valid
During normal operation when power
is on.
When SW4-1 in ON.
Switch set timing
When on
Invalid 2 hours
after compressor
starts.