Control Of Bc Controller - Mitsubishi Electric PURY-80TMU Service Handbook

City multi
Table of Contents

Advertisement

[2] Control of BC Controller

(1) Control of SVA, SVB and SVC
SVA, SVB and SVC are turned on and off depending on connection mode.
Mode
Connection
SVA
SVB
SVC
(2) Control of LEV
LEV opening (sj) is controlled corresponding to operation mode as follows:
Operation mode
LEV1
LEV3
Superheat
*1
control
Differential
*2
pressure control
*3
* The above parts of BC controllers are color-corded and shown with the name plate inside the BC controller unit.
Cooling
ON
OFF
ON
Cooling-only
Heating-only
2000
60
Superheat
Differential
control *1
Pressure control
*2
Control every minute so that superheat amount detected by bypass inlet and oulet
temperatures (TH12, TH15) stay in the specified range.
Control every minute so that detected differential pressure (PS1, PS3) stay in the
specified range.
60 or more pulses are sometimes detected because of rise in liquid side pressure (PS1).
Heating
Stop
OFF
OFF
ON
OFF
OFF
OFF
Cooling-main
Heating-main
• Liquid level
control *3
• Differential
Pressure control
pressure control
*2
–37–
Defrost
OFF
OFF
OFF
(Number of pulse)
Stop
60
2000
Differential
60
*2