Mitsubishi Electric PURY-80TMU Service Handbook page 20

City multi
Table of Contents

Advertisement

2 Heating
Items
Indoor
Ambient temp.
Outdoor
Quantity
Quantity in operation
Indoor unit
Model
Main pipe
Branch pipe
Piping
Total piping length
Indoor unit fan notch
Refrigerant volume
Compressor volts / Frequency
Outdoor unit total current
Indoor unit
BC controller (1, 3)
Oil return
High pressure/Low pressure
BC controller liquid/Intermediate
Discharge (TH1)
Heat exchanger outlet (TH5)
Outdoor
Accumulator
unit
Suction (Comp)
Shell bottom (Comp)
LEV inlet
Indoor
unit
Heat exchanger outlet
Outdoor unit
DB/WB
Q'ty
m
5(16.4) 5(16.4) 5(16.4) 5(16.4) 5(16.4) 5(16.4) 5(16.4) 5(16.4)
(Ft)
kg(oz)
V
V/Hz
A
Pulse
MPa
(psi)
Inlet
Outlet
˚C
(˚F)
–19–
PURY-80TMU(-A)
21.1˚C(70˚F)
8.3˚C(47˚F)/6.1˚C(43˚F)
4
4
24
24
20
10
5(16.4)
25(82)
Hi
Hi
Hi
Hi
10 kg(67 oz)
208
230
149/85
149/85
27.5
24.9
600
950
750
400
60
700
150
1.81/0.35
(263/51)
1.72/1.37
(249/199)
100(212)
–2(28)
–1(30)
–4(25)
–1(30)
45(113)
38(100)
80(176)
PURY-100TMU(-A)
21.1˚C(70˚F)
8.3˚C(47˚F)/6.1˚C(43˚F)
4
4
48
16
24
10
5(16.4)
25(82)
Hi
Hi
Hi
Hi
12 kg(86 oz)
208
230
174/100
174/100
35.6
32.2
750
600
950
400
60
800
235
1.76/0.36
(256/53)
1.67/1.37
(242/199)
95(203)
–1(30)
–1(30)
–2(28)
–1(30)
40(104)
40(104)
85(185)