7-2. FUNCTION OF DIP-SWITCH

Switch Pole
Function
Thermistor<Intake temperature
1
detection>position
2
Filter clogging detection
3
Filter life
4
Air intake
SW1
5
Remote indication switching
Mode
6
Humidifier control
Selection
7
Air flow st
8
Heat thermostat OFF
9
Auto reset function
10
Power ON/OFF
MODELS
PEFY-
P20VMM-E
SW2
Capacity
PEFY-
1~6
P25VMM-E
code
setting
PEFY-
P32VMM-E
PEFY-
P40VMM-E
1
Heat pump/Cool only
2
Louver
3
Vane
4
Vane swing function
5
SW3
Vane horizontal angle
Function
6
Vane cooling limit angle setting
Selection
7
Heating 4deg up
8
9
10
P20~P80
SW4
ON
OFF
Unit
1~4
Selection
Note
:The DipSW setting is effective during unit stopping ( remote controller OFF ) for SW1,2,3 and 4 commonly and the
power source is not required to reset.
:When both SW1-7 and SW1-8 are being set to ON, the fan stops at the heating thermostat OFF.
ON
Built-in remote controller
Provided
2,500hr
Effective
Thermostat ON signal indication Fan output indication
Operational while the heat is ON
Low
Setting air flow
Effective
Effective
SW2
MODELS
ON
ON
PEFY-
OFF
OFF
P50VMM-E
1 2 3 4 5 6
ON
ON
PEFY-
OFF
OFF
P63VMM-E
1 2 3 4 5 6
ON
ON
PEFY-
OFF
OFF
P71VMM-E
1 2 3 4 5 6
PEFY-
ON
ON
OFF
OFF
P80VMM-E
1 2 3 4 5 6
Cooling only
Available
Available
Available
Second setting
Horizontal angle
Not effective
P100~P140
ON
OFF
1 2 3 4
<At delivery>
Operation by switch
OFF
Indoor unit
Not provided
100hr
Not effective
Operational, depending on the condition
Extra low
Reset to SW1-7
Not effective
Not effective
SW2
MODELS
ON
PEFY-
OFF
P100VMM-E
1 2 3 4 5 6
1 2 3 4 5 6
ON
PEFY-
OFF
P125VMM-E
1 2 3 4 5 6
PEFY-
ON
P140VMM-E
OFF
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
Heat pump
Not available
Not available
Not available
First setting
Down blow
Effective
1 2 3 4
Remarks
Address board
Indoor controller board
SW2
Set while the unit is off.
<At delivery>
Set for each capacity.
1 2 3 4 5 6
Indoor controller board
Set while the unit is off.
Indoor controller board
Set while the unit is off.
16