Mitsubishi Electric PURY-80TMU Service Handbook page 112

City multi
Table of Contents

Advertisement

No
SW1
Item
12345678910
52
0010110000
THHS Data
53
1010110000
HPS Data
54
0110110000
TH7 Data
55
1110110000
56
0001110000
57
1001110000
58
0101110000
LPS Data
59
1101110000
60
0011110000
61
1011110000
Accumulator Level
62
0111110000
HzAK Increase/
Decrease
63
1111110000
Difference from
Target Tc
(Tcm-Tc)
64
0000001000
Difference from
Target Te
(Tem-Te)
65
1000001000
Tc
66
0100001000
Te
67
1100001000
Tcm
68
0010001000
Tem
69
1010001000
Comp Frequency
70
0110001000
INV Output
Frequency
71
1110001000
AK
72
0001001000
SLEV
73
1001001000
BC Address
74
0101001000
FANCON Output
Value (Toff%)
75
1101001000
INV Output
Current (IAC)
76
0011001000
OC Address
77
1011001000
IC1 Address/
Capacity Code
78
0111001000
IC2 Address/
Capacity Code
79
1111001000
IC3 Address/
Capacity Code
80
0000101000
IC4 Address/
Capacity Code
81
1000101000
IC5 Address/
Capacity Code
82
0100101000
IC6 Address/
Capacity Code
Note : ˚C scale (˚F scale)
LD1
LD2
LD3
Accumulator Level: 0~9 ("AL=" is also displayed)
Δ Hz
Δ Hz
Δ Hz
0
+
Low
Low
Low
-3˚C
-3 ~ -2˚C
-2 ~ -1˚C
(-5.4˚F)
(-5.4 ~
(-3.6 ~
or lower
-3.6˚F)
-1.8˚F)
Low
Low
Low
-3˚C
-3 ~ -2˚C
-2 ~ -1˚C
(-5.4˚F)
(-5.4 ~
(-3.6 ~
or lower
-3.6˚F)
-1.8˚F)
0 ~ 99
–111–
Display
LD4
LD5
LD6
LD7
-99.9 ~ 999.9
-99.9 ~ 999.9
Δ AK
Δ AK
Stable Region
High
High
1 ~ 2˚C
2 ~ 3˚C
(1.8 ~
(3.6 ~
3.6˚F)
5.4˚F)
Stable Region
High
High
1 ~ 2˚C
2 ~ 3˚C
(1.8 ~
(3.6 ~
3.6˚F)
5.4˚F)
-99.9 ~ 999.9
0 ~ 9999
-99.9 ~ 999.9
0 ~ 9999
0 ~ 99
Remarks
LD8
E*
Δ AK
0
+
High
3˚C
(5.4˚F)
or higher
High
3˚C
(5.4˚F)
or higher
Control Frequency E*
Frequency actually out-
put from the inverter. E*
E*
Displays the FANCON
output value used for
control. E*
(M) Monitored by the
inverter's microcomputer.
E
On the left
(LD1~LD4), the IC
address, and on the
right (LD5~LD8), the
capacity code is
displayed (displayed
alternately every 1
minute).

Advertisement

Table of Contents
loading