Mitsubishi Electric PURY-80TMU Service Handbook page 83

City multi
Table of Contents

Advertisement

(3) Thermistor (Liquid and gas piping temperature detection)
Procedure
1. Remove the service panel
1 Use the procedure under (1)-1.2 to check TH11,
TH12, and TH15.
2. Disconnect the piping sensor lead from the control-
ler panel.
1 TH11 - TH12 (CN10)
2 TH15, TH16 (CN11)
3. Pull the temperature sensor from the temperature
sensor housing and replace it with a new sensor.
4. Connect the temperature sensor lead securely to
the controller board.
(4) Pressure Sensor
Procedure
1. Remove the sensor panel.
1 Use the procedure under (1)-1.2 to check PS1
and PS3.
2. Disconnect the connector of the applicable pressure
sensor from the controller board and insulate the
connector.
1 Liquid pressure sensor (CNP1)
2 Intermediate pressure sensor (CNP3)
3. Install a new pressure sensor at the location shown
in the photograph, and plug the connector into the
controller board.
Important
1 In the case of gas leakage from the pressure sen-
sor, take actions to fix the leak before performing
the above procedure.
Be careful when removing heavy parts.
TH11
TH15
TH16
TH11
TH12
PS1
PS3
PS1
PS3
–82–
Photos
Photos

Advertisement

Table of Contents
loading

Table of Contents