Mitsubishi Heavy Industries SRK20ZJX-S Service Manual page 116

Hide thumbs Also See for SRK20ZJX-S:
Table of Contents

Advertisement

Error code
Remote controller:
E60
1. Applicable model
All models
2. Error detection method
Compressor rotor position
3. Condition of Error displayed
If it fails again to detect the
rotor position after shifting to
the compressor rotor position
detection operation, the
compressor stops.
4. Presumable cause
• Defective outdoor main PCB
• Anomalous power supply
voltage
• Improper refrigerant amount
and refrigerant circuit
• Defective compressor (motor,
bearing)
Note: Insulation resistance
• The unit is left for long period without power supply or soon after installation, migrated liquid refrigerant may dissolve in the refrigerant oil in the compressor.
In such case insulation resistance decreases upto several M or lower. If the electric leakage breaker is activated due to low insulation resistance, check followings.
Check whehter the insulation resistance can recover or not, ater 6 hours has passed since power ON.
(By energize the crankcase heater, migrated liquid refrigerant in the refrigerant oil in compressor can be evaporated)
Check whether the electric leakage breake conforms to high-hermonic specifications
(As units has inverter, in order to prevent from improper operation, be sure to use high-hermonic one.)
LED
Green
Red
Keeps flashing
Stays OFF
Indoor
Outdoor
7 times flash
5. Troubleshooting
Diagnosis
Is the
power supply voltage
OK?
YES
Reset the power supply and restart operation.
Does the compressor start?
YES
Is the
output from inverter
checker OK?
YES
Is the noise
or vibration of compressor
normal?
YES
Does it
start up normally without
recurrence of
E60.
YES
115
-
Content
Compressor rotor lock error
NO
NO
Does E59 occur?
YES
NO
Does the
compressor run without
occurrence of
E42?
NO
NO
NO
-
'10 • SCM-SM-094
Countermeasure
Check and correct the
power supply voltage
Correct it based on the
troubleshooting of E59
Correct it based on the
NO
troubleshooting of E42
Defective outdoor main
PCB Replace.
Replace compressor.
Check compressor for
insulation, resistance.
Replace compressor if
necessary.
Defective outdoor main
PCB Replace.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents