Bellfires DERBY LARGE 3 CF Installation Instructions Manual page 11

Gas fire with closed combustion system
Table of Contents

Advertisement

Bellfi res
1.5.1.2. Positioning the outlet to avoid affecting the surrounding area
All listed "distances" in this section are no more than
guidelines.
For the exact minimum "distances", please consult your
national and local directives.
"Distance" = minimum distance required for positioning of the outlet to avoid
adverse effects with respect to:
A. A ventilation opening serving an occupied room, a toilet or a bathroom.
B. A heating air supply, when the supply fl ows through an occupied room.
C. A window that can be opened and that is near an occupied room, a toilet
or a bathroom.
Roof-mounted outlet:
To avoid adverse effects
At the same roof level.
At a different roof level.
At a lower positioned wall.
At a higher sloping surface.
(*)
If the required distance cannot be achieved, the outlet position rules take
precedence.
(**) If the required distance cannot be achieved, the position of the outlet must
be at least 1 m above the highest facade/roof.
Installation instructions
Distance: outlet - A, B or C
>3 m (*)
>1 m (*)
>1 m
>3 m (**)
English
11