4.9.23 - RESETCFG menu
NAME
FORMAT
COOLING RESET
oatcr_no
-10 to 51.7
oatcr_fu
-10 to 51.7
dt_cr_no
0 to 13.9
dt_cr_fu
0 to 13.9
cr_deg
-16.7 to 16.7
HEATING RESET
oathr_no
-10 to 51.7
oathr_fu
-10 to 51.7
dt_hr_no
0 to 13.9
dt_hr_fu
0 to 13.9
hr_deg
-16.7 to 16.7
4.9.24 - USERCONF menu
NAME
FORMAT
language
0 to 4
use_pass
1 to 9999
4.9.25 - DATETIME menu
NAME
FORMAT
hour
0 to 24
minutes
0 to 59
dow
1 to 7
tom_hol
No/Yes
tod_hol
No/Yes
dlig_off
No/Yes
dlig_on
No/Yes
d_of_m
1 to 31
month
1 to 12
year
0 to 99
4.9.26 - Menu CTRL_ID
NAME
FORMAT
elemt_nb
1 to 239
bus_nb
0 to 239
baudrate
9600 to 38400
4.9.27 - OCCx P0xS menu
The control provides three timer programs: schedule 1,
schedule 2 and schedule 3, that can be activated.
The first timer program (schedule 1) provides a means to
automatically switch the unit from an occupied mode to an
unoccupied mode: the unit is started during occupied periods.
The second timer program (schedule 2) provides a means to
automatically switch the active setpoint from an occupied
setpoint to an unoccupied setpoint: cooling setpoint 1 is used
during occupied periods, cooling or heating setpoint 2 during
unoccupied periods.
The third timer program (schedule 3) allows the unit to switch
to the domestic hot water production mode. The DHW mode is
allowed during occupied periods.
14
DEFAULT
UNIT
-10
°C
-10
°C
0
^C
0
^C
0
^C
-10
°C
-10
°C
0
^C
0
^C
0
^C
DEFAULT
UNIT
0
-
11
-
DEFAULT
UNIT
hours
minutes
No
-
No
-
-
-
DEFAULT
UNIT
1
-
0
-
9600
-
PRO-DIALOG + 30WG
CSA-SR-20H450NN
-
Each schedule consists of eight time periods set by the operator.
These time periods can be flagged to be in effect or not in effect
on each day of the week plus a holiday period. The day begins
at 00.00 hours and ends at 23.59 hours.
Program is in unoccupied mode unless a schedule time period is in
effect. If two periods overlap and are both active on the same
day, the occupied mode takes priority over the unoccupied
period.
Each of the eight periods can be displayed and changed with
the aid of a sub-sub-menu. The table on page 17 shows how to
access the period configuration. Method is the same for the time
schedule 1 or the time schedule 2.
DESCRIPTION
Outside temperature for no reset
Outside temperature for maximum reset
Delta T for no reset
Delta T for maximum reset
Cooling reset value
Outside temperature for no reset
Outside temperature for maximum reset
Delta T for no reset
Delta T for maximum reset
Heating reset value
DESCRIPTION
Language selection
English = 0, Spanish = 1, French = 2, Portuguese = 3, Italian = 4,
Translation = 5
User password
DESCRIPTION
Hour
Minutes
Day of the week
Holiday tomorrow?
Holiday today
Winter time changeover active?
Summer time changeover active?
Day of the month
Month
Year
DESCRIPTION
Element number
Bus number
Communication speed
Description
Software version
Serial number