6. Defrost control


In heating operation, defrost operation is performed when TE sensor temperature satisfies any condition
in A zone to C zone.
The defrost operation is immediately finished if TE sensor temperature has become 12°C or more, or it
also is finished when condition of 5°C < TE < 12°C has continued for 80 seconds.
The defrost operation is also finished when defrost operation has continued for 15 minutes even if TE
sensor temperature has become 5°C or lower.
ƒ
After defrost operation has finished, the compressor and the outdoor fan start heating operation after
stopped for approx. 40 seconds.
Start of heating operation
0
TE [˚C]
–4
–6
–10
–25
* The minimum TE value between 10 and 15 minutes after heating operation has started is stored in memory as TE0.
A zone
Defrost operation is performed in this zone when TE0-TE > 2.5 continued for 20 seconds.
B zone
Defrost operation is performed in this zone when TE0-TE > 3 continued for 20 seconds.
C zone
Defrost operation is performed when this zone continued for 20 seconds.
10
15
*
29
35
A zone
A zone
A z
B zone
B zone
B z
one
C zone
C zone
C z
one
– 86 –
[min.]
one
D zone
D z
one