The suppressor provides continuous bi-polar, bi-directional, non-inter-
rupting protection for both the PM and load from damaging high voltage
transients. It is installed in-line with AC input to the PM. Status indicators
verify input and "PROTECTED" conditions and alarm contacts indicate
when the unit has tripped and equipment is in the unprotected mode. Two
models are available for 115V and 230V applications. Contact the factory
for more information on how to obtain this transient suppressor.

VI) SPECIFICATIONS

All Models
Input: 90-264 VAC, 47-63 Hz.
Power Factor: .96-.99
Regulation: ± 2% at V OUT (through "oring" diode)
Ripple P-P: 1%
Efficiency: 80-85% @ full load
Output Voltage Adjustment Range: ± 10 %
Temperature Rating: 0° to +60° C derate linearly from 100% load @ 50°
C to 80% load at 60° C
Altitude Operational Rating: Full output to 5,000 feet; reduce output
current 4% per 1,000 feet
above 5,000 feet; 10,000 feet maximum
Individual Model Specifications
Model
Input
Amps
V OUT
@ F.L.
115/230V
PM-12-40
8.5/4.3
13.6
PM-12-70
16/8
13.6
PM-24-20
8.5/4.3
27.2
PM-24-35
16/8
27.2
PM-48-10
8.5/4.3
54.4
PM-48-18
16/8
54.4
† For parallel configuration/load sharing derate output 10%
Protection
Output fuse for reverse polarity
Current limit and foldback
Input circuit breaker
Automatic high temperature protection
Case Size:
3.5" H x 17" W* x 20.5" D
* 19" and 23" mounting brackets provided
Certifications
• EN 55022 (Conducted)
• FCC Part 15, Level A (Radiated)
7
P.O. Box 1306
Newport Beach
California 92663
Output
Recommended
V2
Amps
Battery
Cont.†
Capacity
(Amp/Hours)*
14.3
40
80-400
14.3
70
140-700
27.9
20
40-200
27.9
35
70-350
55.1
10
18-90
55.1
18
36-180
Weight
Lbs
Kg.
12.2
5.5
15.2
6.9
12.2
5.5
15.2
6.9
12.2
5.5
14.0
6.4
Phone: 714-751-0488
Fax: 714-957-1621