5.0 – SPECIFICATIONS
Table 5.0.1 – Electrical & Operating Specifications
PARAMETER
INPUT
AC Input Voltage
Input Frequency
Power Factor Correction
AC Input Current (note 1)
DC Input Voltage
DC Input Current (note 1)
Input Fuse Trip Current
OUTPUT – Battery & Load
Battery & Load Voltage (note 2)
At 25°C
Battery & Load Voltage (note 2)
Over 0 – 60°C (temp. comp.
range)
Output Voltage Temperature
Compensation (0 – 60°C only)
Battery Charging Current (no
load)
Quiescent Battery Current
(LINE-DOWN mode – no load)
Load Current
Output Switching Noise (note 3)
GENERAL
Operating Temperature
Operating Humidity
Efficiency
EMC – Emissions
Radiated Noise: 30mHz – 1gHz per FCC Class B
Conducted Noise: 150kHz – 30mHz per FCC Class B
ALARM CONTACTS
DC Current Rating at 30 VDC max
AC Current Rating at 120 VAC
max
Contact Isolation Voltage
NOTES:
1. These values apply at minimum input voltage conditions.
2. The stated voltages refer to system in LINE-UP mode with a fully charged battery. If the battery has
been recently discharged the system will operate in current limited mode until the battery regains full
charge. When the battery is less than fully charged, the output voltage will be lower than the stated
values. In LINE-DOWN mode, the load voltage is roughly equal to the battery voltage. Battery voltage
will be a function of state of charge, temperature and overall condition. In both modes of operation
the LOAD voltage will be as much as 0.2 Volts (0.4 Volts for 24 Volt systems) lower than the battery
voltage because of the parasitic voltage drop across the output switch.
3. The system battery has a significant damping effect on noise; typical output noise will be much lower.
Table 5.0.2 – Replaceable Parts
EP 12-10
MIN.
TYP.
MAX.
85
265
47
66
0.95
2.6
110
370
2.0
5
13.7
13.8
13.9
12.9
14.9
(60° C)
(0° C)
−0.025
10.5
0.02
10.0
100
−20
60
10
95
75
1.0
0.3
500
EP 24-5
MIN.
TYP.
MAX.
85
265
47
66
0.95
2.6
110
370
2.0
5
27.4
27.6
27.8
25.8
29.8
(60° C)
(0° C)
−0.05
5.25
0.02
5
100
−20
60
10
95
78
1.0
0.3
500
5
UNIT
Volts RMS
Hertz
n/a
Amps RMS
Volts
Amps
Amps
Volts
Volts
(ambient temperature)
Volts / °C
Amps
Amps
Amps
mV p-p
°C
% R.H. non-condensing
%
Amps
Amps
Volts RMS