High Elevation; Gas Line Installation; Pilot Adjustment; Gas Pipe Pressure Testing - Outdoors Outdoor 42 Owners & Installation Manual

Gas fireplace
Table of Contents

Advertisement

installatiOn
OD42-N SYSTEM DATA
Max. Supply Pressure
14" WC (3.49 kpa)
Min. Supply Pressure
5" WC (1.25 kpa)
Manifold Pressure
3.5" WC (0.87 kpa)
Orifice Size
#29 DMS
Maximum Input
44,500 Btu/h
(13.04 kW)
OD42-P SYSTEM DATA
Max. Supply Pressure 14" WC (3.49 kpa)
Min. Supply Pressure
11" WC (2.73 kpa)
Manifold Pressure
10" WC (2.49 kpa)
Orifice Size
#47 DMS
Maximum Input
43,500 Btu/h
(12.74 kW)

hIGh ELEvATION

This unit is approved for altitude 0 to 4500 ft. (CAN1
2.17-M91).
GAS LINE
INSTALLATION
Since some municipalities have additional local
codes it is always best to consult with your local
authorities and the CAN/CGA B149 installation
code.
For USA installations follow local codes and/or the
current National Fuel Gas Code, ANSI Z223.1.
When using copper or flex connectors use only
approved fittings. Always provide a union so that
gas lines can be easily disconnected for servicing.
Flare nuts for copper lines and flex connectors are
usually considered to meet this requirement.
NOTE: A shutoff / dante key valve should be
supplied in or near the unit (or as per local
codes) for ease of servicing this appliance.
IMPORTANT: Always check for gas leaks with
a soap and water solution or gas leak detector.
Do not use open flame for leak testing.
14

PILOT ADjUSTMENT

Periodically check the pilot flames. correct flame
pattern has two strong blue flames: 1 flowing
around the flame sensor and 1 flowing across
the burner (it does not have to be touching the
burner).
Burner
Flame Sensor
Pilot
Note: If you have an incorrect flame pattern,
contact your Firegear
®
for further instructions.
Incorrect flame pattern will have small, probably
yellow flames, not coming into proper contact
with the rear burner or flame sensor.
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas supply
piping system by closing its individual manual shut-
off valve during any pressure testing of the gas
supply piping system at test pressures equal to or
less than 1/2 psig. (3.45 kPa). Disconnect piping
from valve at pressures over 1/2 psig.
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note: To properly check gas pressure, both
inlet and manifold pressures should be
checked using the valve pressure ports
on the valve.
1) Make sure the valve is in the "OFF" position.
2) Loosen the "IN" and/or "OUT" pressure tap(s),
turning counterclockwise with a
1/8" wide flat screwdriver.
3) Attach manometer to "IN" and/or "OUT" pressure
tap(s) using a 5/16" ID hose.
4) Light the pilot and turn the valve to "ON" position.
5) The pressure check should be carried out with
the unit burning and the setting should be within
the limits specified on the safety label.
6) When finished reading manometer, turn off the
gas valve, disconnect the hose and tighten the
screw (clockwise) with a 1/8" flat screwdriver.
Note: Screw should be snug, but do not over
tighten.
880 S.I.T. vALvE
1) Pilot adjustment
2) Outlet Pressure Tap
3) Inlet Pressure Tap
4) Pilot Outlet
5) Main Gas Outlet
6) Main Gas Inlet
3
Ignitor
Outdoors dealer
4

AERATION ADjUSTMENT

The burner aeration is factory set but may need
adjusting due to either the local gas supply or
altitude. Open the air shutter for a blue flame or
close for a more yellow flame.
Minimum Air Shutter Opening:
1/8"
1/4"
Note: Any damage due to carboning resulting
from improperly setting the aeration
controls is NOT covered under warranty.
To Adjust Aeration:
1. Follow Steps 1-12 in Valve Replacement instruc-
tions (in this manual).
2. Adjust aeration accordingly.
3. Reverse Steps 1-12.
DEScRIPTION
2
1
6
5
NG
LP
OD42 Outdoor Gas Fireplace