Protective Function List - Fujitsu Airstage J-II Service Manual

Small vrf system
Hide thumbs Also See for Airstage J-II:
Table of Contents

Advertisement

2-6 PROTECTIVE FUNCTION

2-6-1 Protective Function List

Protective Function
Detect Parts
Discharge Temp
Discharge Temp
Protection 1
Thermistor
Discharge Temp
Discharge Temp
Protection 2
Thermistor
Discharge Temp
Discharge Temp
Protection 4
Thermistor
Discharge Temp
Discharge Temp
Protection 5
Thermistor
Discharge Temp
Discharge Temp
Protection Stop
Thermistor
High Pressure
High Pressure
Protection 1
Sensor
High Pressure
High Pressure
Protection 2
Sensor
High Pressure
High Pressure
Protection 3
Sensor
High Pressure
High Pressure
Protection 4
Sensor
High Pressure
High Pressure
Protection 5
Sensor
Abnormal High
High Pressure
Pressure Protection
Sensor
Control
COOL HEAT
DISPLAY
<Starting conditions>
3 minutes have elapsed since the start of operation and
(discharge temperature
30 minutes)
<Reset conditions>
Discharge temperature
<Starting conditions>
Cooling: Discharge temperature
Heating: Discharge temperature
< starting condition>
Discharge temperature
<Starting conditions>
Discharge temperature
<Reset conditions>
2 minutes have elapsed and
(discharge temperature
P1
<Pattern
starting condition>
Discharge temperature
<Pattern
reset condition>
3 minutes have elapsed and discharge temperature
EA11
<Pattern
starting condition>
Pattern
generated 2 times within 40 minutes
<Pattern
reset condition>
Error reset (push button SW) executed after power turned on again
<Starting conditions>
COMP < 25 rps ---- HP
25 rps
COMP < 30 rps ---- HP
30 rps
COMP
<Reset conditions>
Fixed time has elapsed and Fixed time when SV2: ON 30 secs
COMP < 25 rps ---- HP
25 rps
COMP < 30 rps ---- HP
30 rps
COMP
<Starting conditions>
COMP
COMP < 25 rps ---- HP
<Reset conditions>
3 minutes have elapsed and high-pressure
<Starting conditions>
Fixed time has elapsed and high-pressure
(* Fixed time at start of operation: 10 secs, after operation execution: 20 secs)
<Reset conditions>
Operation (fan speed 1 step increase) complete
<Pattern
starting condition>
High-pressure
<Pattern
starting condition>
High-pressure
<Starting conditions>
High-pressure
<Pattern
starting condition>
COMP < 30 rps ---- HP
COMP
<Pattern
reset condition>
After 25 seconds have elapsed and,
COMP < 30 rps ---- HP
COMP
<Pattern
starting condition>
COMP
COMP
<Pattern
reset condition>
After 25 seconds have elapsed and,
COMP
COMP
Operating Condition
100°C or suction SH
10°C accumulated time
95°C and suctionSH
7°C
<Reset conditions>
95°C
Discharge temperature
102°C
Discharge temperature
<Pattern
reset condition>
105°C
Discharge temperature
95°C and EEV1=500pls
90°C or EEV1
400pls)
fixed value (115°C)
80°C
3.3 MPa
3.5 MPa
---- HP
3.8 MPa
3.0 MPa
3.2 MPa
---- HP
3.5 MPa
25 rps ---- HP
3.5 MPa
3.3 MPa
2.80MPa
3.50MPa
<Pattern
reset condition>
3.30MPa
High-pressure
<Pattern
reset condition>
3.50MPa
High-pressure
<Reset conditions>
3.20MPa
High-pressure
3.18 MPa
30 rps ---- HP
3.68 MPa
3.1 MPa
30 rps ---- HP
3.6 MPa
30 rps ---- HP
3.3 MPa
30 rps ---- HP
3.8 MPa
30 rps ---- HP
3.18 MPa
30 rps ---- HP
3.68 MPa
02-11
EEV of operating indoor unit gradually opened
EEV2 + 30pls/30 secs
90°C
97°C
Compressor speed -6rps every 30 secs
100°C
Speed rise prohibited,
when discharge temperature becomes lower
than 105 , prohibit the rotational speed rise
of the compressor.
Expansion valve of stopped indoor unit gradually
opened
(upper limit 200pls)
Compressor stopped
Compressor stopped
(permanent stop)
Error display
SV2 ON
SV2 ON
Fan speed 1 step increase
Fan speed lowered/every 30 secs
3.2MPa
Fan lowest speed
Upper 270 rpm
3.5MPa
Lower 250 rpm
Compressor capacity lowered/every 15 secs
3.20MPa
Compressor capacity rise prohibited
Compressor capacity lowered every 30 secs
Operation