Thermistor Resistance - Fujitsu Airstage J-II Service Manual

Small vrf system
Hide thumbs Also See for Airstage J-II:
Table of Contents

Advertisement

5-3-2

Thermistor resistance

Thermistor resistance value <Outdoor unit side>
Temperature
[°C]
Thermistor A
- 20
---
- 10
---
- 5
---
0
168.6
5
129.8
10
100.9
15
79.1
20
62.6
25
49.8
40.0
30
40
26.3
50
17.8
60
12.3
70
8.7
80
6.3
90
4.6
100
3.4
110
2.6
120
2.0
Discharge temp. TH1
Applicable
Comp.1 temp. TH10
Thermistors
Thermistor resistance value <Indoor unit side>
Indoor Temperature
Thermistor (TH21)
Temperature (°C)
Resistance Value (
)
Temperature (°C)
Resistance Value (
)
Heat Exchanger Thermistor (Inlet TH22 /
Temperature (°C)
Resistance Value (
)
Temperature (°C)
Resistance Value (
)
Resistance Value [ k ]
Thermistor B
Thermistor C
---
105.4
27.8
58.2
21.0
44.0
16.1
33.6
12.4
25.9
9.6
20.2
7.6
15.8
6.0
12.5
4.8
10.0
3.8
8.0
2.5
5.3
1.7
3.6
1.2
---
---
---
---
---
---
---
---
---
---
---
---
---
Heat exchanger. TH5
Outdoor temp. TH3
Suction temp. TH4
Sub-cool heat exchanger
Gas (inlet) TH8
Sub-cool heat exchanger
Gas (outlet) TH9
Sub-cool heat exchanger
Liquid temp TH7
0
5
10
33.6
25.2
20.1
40
45
50
5.3
4.3
3.5
Outlet TH23)
0
5
10
168.6
129.8
100.9
40
45
50
26.3
21.2
17.8
15
20
25
15.8
12.5
10.0
15
20
79.1
62.5
49.8
05-20
30
35
8.0
6.5
25
30
35
40.0
32.4

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Airstage j-iis

Table of Contents