4-1-2 OUTDOOR UNIT DISPLAY

Indication type
Idling(stop)
Cooling Mode
Heating Mode
Oil Recovery Operation
Defrost Operation
System stooped with Discharge Temp.
Protection
System stopped with High Pressure
Protection
System stopped with Low Pressure
Protection
System stopped with compressor Temperature
Protection
Peak Cut Mode
Low Noise Mode
Inverter Compressor Operation Indication
POWER
MODE
LED101
(GREEN)
LED105
7 Segment LED Pattern
ERROR
POWER
LED101
LED102
(RED)
LED104
ERROR
LED102
Blank
"C" OO "L"
"H" EA "T"
Refer to 02-10 page for operation.
"O" IL "R" ECOVERY
Refer to 02-11 page for operation.
"D" E "F" ROST
<Starting condition>
Discharge temp
<Release condition>
3 minutes have elapsed and discharge temperature
"P" ROTECT "1"
<Starting condition>
High pressure
<Release condition>
5 minutes have elapsed and high pressure
"P" ROTECT "2"
<Starting condition>
Low pressure
or low pressure
<Release condition>
"P" ROTECT "3"
3 minutes have elapsed and low pressure
<Starting condition>
Compressor temp
<Release condition>
3 minutes have elapsed and discharge temperature
"P" ROTECT "4"
"P" eak "C" ut
Refer to 02-08 page for operation.
"L" OW "N" OISE
ON
OFF
Blinking
ON
OFF
ON
OFF
04-02
Description
fixed value: 115°C
80°C
4.00MPa
3.50MPa
0.05MPa
0.10MPa continues for 10 minutes
0.17MPa
fixed value :110°C
80°C
1 sec
1 sec