Oil Recovery Operation; Special Operation - Fujitsu Airstage J-II Service Manual

Small vrf system
Hide thumbs Also See for Airstage J-II:
Table of Contents

Advertisement

2-5 SPECIAL OPERATION

2-5-1 Oil Recovery Operation

Purpose of the operation
The amount of refrigerant lubricant oil which has been transported to the indoor units
and the connection pipe with the refrigerant will become large as the operation time of compressor increases.
It is necessary to recover the oil back into the outdoor unit for a certain time interval
in order to prevent compressors from damaging due to lack of lubrication oil.
1. Oil Recovery in Cooling operation
<
Start condition >
Compressor accumulated operation time since last cooling oil recovery operation exceeds 3 hours (first time : 1hour)
< End condition >
30 seconds have elapsed since the start and "suction temperature - low pressure saturation temperature
have elapsed since the start.
< Operation >
COMPRESSOR: The rotation speed varies depending on the operation state.
EEV Opening (Indoor/Outdoor unit): Controlled pulse (as normal operation mode).
FAN speed (Indoor/Outdoor unit)
2. Oil Recovery in Heating operation
< Start condition >
Compressor accumulated operation time since the last heating oil recovery exceeds 8 hours (first time : 1hour)
< End condition >
After 4 minutes have elapsed
< Operation >
COMPRESSOR: The rotation speed varies depending on the operation state.
EEV Opening (Indoor/Outdoor unit) : Controlled pulse (as normal operation mode)
FAN speed (Indoor/Outdoor unit)
Others
During the oil recovery operation,
and
appears on the simple remote controller.
The operation indicators (LED) of the indoor units flash slowly.
: Controlled fan speed (as normal operation mode).
: Controlled fan speed (as normal operation mode)
appears on the display of wired and central remote controller,
02-09
5deg" or 6 minutes

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Airstage j-iis

Table of Contents