Technical Data - Bicker UPSI-2403 User Manual

Dc ups system
Table of Contents

Advertisement

Available languages

Available languages

2 Technical Data of the DC UPS UPSI-2403
T e c h n i c a l d a t a
Input voltage
Input current
Output voltage
Output current
Battery charge current
Charging method
Protection
Transfer time / limits
Interface
Type of battery
Safety / EMC
Temperature
Humidity
Dimensions (W x D x H)
Weight (net)
P r o d u c t s p e c i f i c d a t a
LED display
Battery monitoring
Power consumption
Shutdown-suppression
Reboot function
Back up time
The service life of the batteries is app. 4...5 years at +20 °C and will decrease by half with each temperature increase of 10 °C according
to EUROBAT.
18
24 V DC (22.5...28 V)
6.7 A max.
In normal mode: app. 0.5 V below input voltage
In battery mode: app. 29...19 V DC
6 A max.
0.65 A max. (internal battery charger)
UI characteristic, with temperature regulation
Deep dircharge protection: 19 V DC ±2 %
Overload protection at output: 9 A for 2 seconds, switch off
Short-circuit protection: Switch off via µC
Mains / battery 20 V DC ±2 %, batteriy / mains 22 V DC ±2 %
USB (Standard B)
Equipped lead-gel-battery, maintenance-free, 1.3 Ah
CE
Operating: 0...+40 °C / Storage: -10...+40 °C
Operating: 10...85 % RH, non-condensing
Storage: 10...90 % RH, non-condensing
90 x 100 x 121 ±0.5 mm
2 kg
3-colour-LED for „Power ok" (green), „Power Fail" (orange),
„Battery low" (red/orange flashing) and „Battery defect"
(red/green flashing), short circuit at output/overload (red)
Battery test is carried out in normal mode approx every 10 minutes,
in case of "Battery defect" notification the LED flashes red/green
App. 80 mA
During system start-up the shutdown signal is suppressed for app. 2 min.,
because any interface testing of Windows and a simultaneous power
failure would switch off the module. This suppression is only active when
the module is switched on the first time!
If power fails and then returns during the shutdown mode of Windows®,
the operating system will ‚lock' with the message „Your PC is now safe".
The reboot function restarts the system after about 10 seconds.
App. 33 min at 1 A / app. 9 min at 3 A / app. 3.5 min at 5 A
(measured at +20 °C)
User's Manual UPSI-2403

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

Table of Contents