Test For Flue Spillage; Log & Ember Installation - Regency F33-NG1 Owners & Installation

F33 freestanding
Table of Contents

Advertisement

INSTALLATION

TEST FOR FLUE SPILLAGE

This heater must be properly connected to a flue system.
WARNING: Operation of this heater when not connected to
a properly installed and maintained flue system or tamper-
ing with the flue safety shutoff system can result in carbon
monoxide (CO) poisoning and possible death.
A "spillage" test must be made before the installed unit is left with
the customer. Follow the procedure below:
1)
Start all exhaust fans in the home and then close all doors
and windows in the room.
2)
Light the unit and set controls to maximum.
3)
After five minutes, test that there is a "pull" on the flue by
placing a smoke match, cigarette or similar device which
gives off smoke, on the edge of the draft hood. See Diagram
below.
The smoke should be drawn into the draft hood. If the smoke is
still not drawn into the draft hood, turn the unit off and check for
the cause of the lack of draft and rectify before proceeding.
Note: If the flue is blocked or has a strong reverse flow, the
thermally actuated safety switch mounted in the draft hood
will automatically shut off the gas supply in less than 10
minutes. If the heater turns off because of this during the
spillage test, check for the cause of the lack of draft and
rectify before proceeding.
To reset the thermally actuated safety switch, let the unit
cool for 10 minutes, then press the red reset button on the
back of the switch. See Diagram.
10
LOG AND EMBER INSTALLATION
WARNING: Dangerous operating conditions may occur if
these logs are not positioned in their approved locations.
Read the instructions below carefully and refer to the
diagrams. If logs are broken do not use the unit until they
are replaced. Broken logs can interfere with the pilot and
burner operation.
The gas log kit contains the following:
a) Front Log
b) Rear Log
c) Small Cross Logs (2)
d) Bag of embers
e) Bag of rock wool
1)
Remove the logs from the box and carefully unwrap them.
The logs are fragile, handle with care. Do not force into
position.
2)
Place the rear deflector on the rear log support pins in the
back of the unit.
3)
Place the rear log into the rear of the firebox, aligning the
holes on the underside of the log with the rear log support
pins and carefully push the log down onto the pins. See
diagrams 1 and 2.
4)
Ensure the front deflector is over front log pins. See diagram
1.
5)
Place the front log in the front of the unit, aligning the holes
on the underside of the log with the log support pins in the
front of the unit. Carefully push the log down onto the pins.
See diagram 1.
6)
Place the cross logs on top of the larger logs aligning the
holes on the underside of the cross log with the log pins in
the larger logs. See diagrams 1 & 2. Carefully push the
cross logs onto the pins.
Diagram 1
Regency F33-1 Freestanding Gas Stove