Sequence Of Operation - Space-Ray PTS 40-N7/L7 Installation And Operation Instructions Manual

Infrared radiant tube heater two stage push through system (positive pressure)
Table of Contents

Advertisement

19.0)

SEQUENCE OF OPERATION

The chart below shows the sequence of operation for the normal operating cycle of the PTS/PTU when
connected to a permanent 120V power supply and the heater is turned on and off by a remote 24V thermostat.
Note:
If the flame is not sensed during sequence T3 then the burner will automatically begin re-ignition sequence T2.
The ignition sequence will be repeated three times with a 60 second inter-purge. If the flame is not re-
established the heater will go to lockout.
Form 43343530
-42-
Aug 2012